Desigo tra mounting and installation

PL-Link devices QMX3. Desigo™ TRA
Mounting and installation
Building Technologies
Contents
Mounting and installation Building Technologies Mounting and installation Building Technologies About this document
1.1 Revision history
Revision Date
Section Page
Wiring of field devices
External KNX bus power supply
• Gamma Instabus Documentation • External bus supply types
1.2 Reference documents
Document title
Document
TX-I/O™ Functions and operation. TX-I/O™ Engineering and installation manual. Desigo Technical principles manual, Section 21. Ethernet, TCP/IP as well as BACnet on Ethernet/IP principles TX-I/O™ Product range overview. TX-I/O™ Module datasheets. Data sheet TX-I/O™ supply module and bus interface module. Data sheet Room units EnOcean QAX9x.4. Data sheet Room units EnOcean QAX95.1, QAX96.1. Data sheet Gateway EnOcean/KNX Desigo PX Mounting and installation guide Data sheet PXC3. Room automation station Data sheet RXM21.1 PL-Link I/O Block Data sheet RXM39.1 PL-Link I/O Block Gamma Instabus documentation: Mounting and installation Building Technologies About this document 1.3 Before you start
1.3.1 Trademarks

The table below lists the third-party trademarks used in this document and their legal owners. The use of trademarks is subject to international and domestic provisions of the law. Trademarks
Legal owner
American National Standard (ANSI/ASHRAE 135- Konnex Association, B - 1831 Brussels-Diegem EnOcean LLC, Germany 82041 Oberhaching ZVEI - Zentralverband Elektrotechnik- und Elektronikindustrie e.V., Stresemannallee 19, D-60596 Frankfurt am Main Al product names listed in the table are registered (®) or not registered (™) trademarks of the owner listed in the table. We forgo the labeling (e.g. using the symbols ® and ™) of trademarks for the purposes of legibility based on the reference in this section.
1.3.2 Copyright

This document may be duplicated and distributed only with the express permission of Siemens, and may be passed on only to authorized persons or companies with the required technical knowledge.
1.3.3 Quality assurance

These documents were prepared with great care. • The contents of all documents are checked at regular intervals. • Al necessary corrections are included in subsequent versions. • Documents are automatical y amended as a consequence of modifications and corrections to the products described. Please make sure that you are aware of the latest document revision date. If you find any lack of clarity while using this document, or if you have any criticisms or suggestions, please contact your local POC at the nearest branch office. Addresses for Siemens RCs are available at Mounting and installation Building Technologies About this document 1.3.4 Document use/ request to the reader
Before using our products, it is important that you read the documents supplied
with or ordered at the same time as the products (equipment, applications, tools etc.) carefully and in full. We assume that persons using our products and documents are authorized and properly trained and have the requisite technical knowledge to use our products as Additional information on products and applications is available: • On the intranet (for Siemens employees only) at • At your next Siemens branch officor at your system • From the support team in the headquarters if no local POC is available. Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
1.4 Document validity

Mounting and installation Building Technologies About this document Introdution
2.1 About this document

Main target audience
The mounting and installation guide is targeted at • Panel builders and factory instal ers
Electricians
Engineers
The mounting and installation guide provides all the information needed by the aforementioned personnel for:
The proper mounting and wiring of Desigo TRA in the instal ation box and
connections to the plant.
An overview of the room automation station product range and its design is
provided for general understanding. Additional use
The mounting and installation guide is provided to internal engineering personnel at Siemens Building Technologies and system houses with information on the following topics: – Installation variants for room automation station. – Regulations and notes. The mounting and installation guide includes all documentation in the form of text and images required fort he aforementioned target groups and intended use. It does not include information of plant-specific mounting and wiring work. This information is available in the appropriate project documentation. Mounting and installation Building Technologies 2.2 What does this document describe?

Overview
The document describes proper mounting and wiring for – the room automation station. – the TX-I/O modules in an installation box or panel. – for peripheral devices connected to the TX-I/O modules. – for peripheral devices connected via PL-Link, DALI and EnOcean. Topology
PL-Link devices QMX3. The areas indicated above can be briefly described as follows: Brief description
Installation boxes. The following devices are installed in the installation box: – PXC3. room automation station. – TX-I/O modules connected to the room automation station via the island bus. Building services Connected plants and systems, including: Heating, ventilation and air conditioning plants, electrical systems, etc., as well as electrical areas (switches, buttons, lighting groups, blinds). Mounting and installation Building Technologies Connections
In general the following connections exist from and to the installation box: • Ethernet
Room automation stations as well as Desigo Insight and the primary plant level PX are connected via Ethernet cables and switches. • Island bus / island bus expansion:
A bus cable runs from the room automation station to the external I/O modules. • Wiring form I/O modules to field devices (sensors, switches/buttons, control
values, motors, etc). • PL-Link
A bus cable runs from the automation station to the PL-Link/KNX devices. A bus cable runs from the automation station to DALI devices. The room automation station includes an USB Device interface. It serves for commissioning and service. ABT and SSA can communicate with the PXC3. via this interface. Furthermore, access to other PXC3. via the network is possible. Al testing and commissioning functions including download, online test etc. are available. For details see SSA (Setup & Service Assistant) Commissio- • Wireless connections:
A KNX gateway integrates wireless EnOcean devices (room units, sensors, Mounting and installation Building Technologies Important information on safety
Please comply with This section deals with general and system-specific regulations. It includes
these notes important information for your safety and the safety of the entire plant.
Sections flagged with the warning symbol to the left contain safety-related Safety notes
requirements and restrictions that must be adhered to at all times to prevent physical injury and equipment damage. Please comply with the following general regulations during engineering and . General
Regulations
execution: • Electrical and mains power ordinances for the given country. • Other applicable, national regulations. • Building instal ation regulations for the given country. • Regulations of the facility supplying electricity. • Diagrams, cable lists, dispositions, specifications and orders by the customer or authorized engineering office. • Third-party regulations, e.g. by the general contractor or building owner.
3.1 System-specific regulations

The electrical safety for building automation and control systems by Siemens Building Technologies is essentially based on safely separating low voltage from
mains voltage.
SELV, PELV
Application as per SELV or PELV pursuant to HD 384 "Electrical installation of buildings" depending on the grounding (⊥ AC24V) of the low voltage: Ungrounded = Safety Extra-Low Voltage (SELV).
Grounded = Protection by Extra Low Voltage (PELV).
Device-related safety is guaranteed, among others, by . Device safety
– Low-voltage power supply AC 24 V per SELV or PELV – Double insulation between mains voltage AC 230 V and SELV/PELV circuits and Comply with specific regulations for electrical wiring per the following sections. . Grounding of
Observe the following points when grounding ⊥ AC 24 V (system neutral): • Operating voltage of AC 24 V is permitted in principle for both grounded as well (System neutral)
as non-grounded system neutral. Local regulations and customers apply • Grounding may be required or not allowed for functional reasons. Recommendation on • AC 24 V systems are general y grounds unless otherwise not recommended
by the manufacturer. • In order to avoid ground loops, connect systems with PELV to the ground at one location only (especially for transformers), if no other indication exists. Mounting and installation Building Technologies Important information on safety The following regulations apply to mains and operating voltage: . Mains and operating
Regulations
Operating voltage It must meet requirements for SELV or PELV. Permitted deviation for nominal voltage AC 24 V on the device: -10 - + • Use safety insulating transformers as per EN 61558 with double insulation designed for 100% duty to supply SELV or PELV circuits. • Power taken from the transformer should be at least 50% of nominal load for efficiency reasons (effectiveness). • Transformer nominal power should be at least 25 VA. For smal er transformers, the ratio of open circuit voltage to full load is unfavorable Transformers on the secondary side correspond to the actual load of all connected devices as per transformer – AC 24 V line (system potential) must always be fused. – We required, an additional line ⊥ (system neutral). Transformer, primary side: Installation box fuse (control circuit fuse). . Caution with regard
Any insertion or drawing of dangerous voltages to the system's low-voltage circuit, to foreign voltages!
e.g. caused by improper wiring directly places people at risk can may result in the partial or complete destruction of the building automation and control system! Al wiring existing the building is at severe risk of over-voltage caused by . Measures against
lightening
atmospheric discharges (lightening). Overvoltages can be inductively, capacitive or galvanically into electronic systems and may cause faults or even destroy sensitive components. This overvoltage must be diverted to the earth to limit the damage. This may be achieved with the help of gas-fil ed surge arrestors, varistors and diodes as well as capacitors and chokes. Specialized companies (e.g. Siemens, Phoenix) combines these elements into protective components to provide optimum protection for various systems. Mains filter
Spikes and high-frequency interference may occur in areas with high levels of interference. The disturbances not only impact the transformer on the primary side, but may also influence secondary connected components. A mains filter should be attached on the primary transformer if such interference is anticipated. Mains filters should be installed as close to the network transformer as possible and grounded. Mounting and installation Building Technologies Important information on safety Emergency intervention
Peak loads occur when switching inductive loads that may cause faults to the of power components
system. In addition, sparks may damage switching contacts. Power components must include effective protection against disturbances to prevent such faults. Inductivity (transformers, fuses, relays) are wired directly at the terminals using transzorbs, MOVs (metalloxyd varistors) or RC elements. The breakdown voltage of the transzorbs or MOVs must equate to the 1.7 to 2 times the applicable nominal voltage. Inductive DC consumers can also be suppressed using diodes or RC elements. The transzorbs, MOVs, diodes or RC elements must be optimally matched to the power components and mounted using short wiring.
3.2 Device-specific regulations

. Field device
connection
Devices using different Devices must have the required insulation of the power circuits from each other to be able to connect them directly without additional insulation. Interfaces for different Connections via interfaces increase the risk of distributing dangerous voltage voltage circuits through the building. Ensure that the required insulation is available at all times and instal ed per applicable regulations. The supply terminals of the PXC3. (terminals 7 and 8) bare a max current of
10 A, otherwise the pins get too warm.
An external T10 A fuse is compulsory
Mounting and installation Building Technologies Important information on safety The il ustration is a diagram of a PXC3 room automation station in an installation box / panel, the TX-I/O modules, connections to the field devices as well as bus connections (Ethernet, PL-Link, DALI). Installation box /
Transformer AC 230 V / AC 24 V PXC3. room automation station. U1, U3 TXS1.EF10Bus connection modules I/O row, supplied by the PXC3. I/O row supplied by a TXS1.EF10Bus connection module TXA1.IBE Island bus expansion module (optional) Mounting and installation Building Technologies Installation box TRA
5.1 Instal ation box requirements

Please comply with Please read Sections 5.1 "Installation box requirements" and 5.2 "EMC compliant
these notes panel" in the TX-I/O engineering and installation guide [2] prior to engineering and
executing the installation box. Space requirements
Observer the following for mounting and installation. – Installation depth – Maintain sufficient cable distance to be able to easily snap on and remove the screw terminal blocks, even if the automation stations are mounted. – Room automation stations can be mounted directly next to one another; a distance of ca. 2 cm is recommended, however, for facilitate access. – Reserve sufficient free space for subsequent extensions. Installation mode
The room automation stations and TX-I/O modules are designed for installation on standard rails (prerequisite to establishing the island bus connection using TX-I/O Permissible standard rails: • Top hat rails TH35-7.5 as per EN60715 (35 x 7.5 mm). • Other top hat rails that meet the following conditions: – Material thickness exterior max. 1 mm, min. 3 mm in depth – Internal opening at least 25 mm. The room automation station may also be attached to a wall if used without TX-I/O Mounting and installation Building Technologies Installation box TRA 5.2 Installation box layout

The table below provides information on general instal ation box requirements. Check to ensure the individual requirements are met. Construction, stability and sealing meet applicable regulations at the plant's location. • Desigo TRA is designed for an ambient temperature of -5 - 50°C. PXC3.: 45°C for certain mounting positions, see below. Please make sure that the installation box is sufficiently ventilated to ensure compliance with the ambient temperature for all devices. • For devices, the permissible values as per the data in "Technical data" in the datasheet must be observed with regard to: – Humidity, vibration. – Device IP class and device protective type. EMC compliant The instal ation box corresponds to the rules described installation box in Secti Mechanical dimensions
The following help to determine the required installation box dimensions: – Data on placement in this section. – Device dimensions in the datasheets [8].
5.3 Geometric design
5.3.1 Mounting position

TX-I/O devices can be mounted in any position:
Recommended
Permissible
• Wall, horizontal from left to right or from right to left • On a horizontal surface. • Wall, vertical from top to bottom or from bottom to top. Ambient temperature -5. 50 °C
Ambient temperature -5. 50 °C

For the PXC3. , the following restrictions apply:
Recommended
With restrictions *)
• Wall, horizontal from left to right or from right to left • On a horizontal surface. • Wall, vertical from bottom to top. • Wall, vertical from top to bottom. Ambient temperature -5. 50 °C
Ambient temperature -5. 45 °C *)
*) 50°C is admissible if the bus supplies use max. 2/3 of the specified load: PL- Link 105mA, DALI 85mA and island bus 400mA. Mounting and installation Building Technologies Installation box TRA Note You must ensure, however, that sufficient ventilation is available to maintain
the permissible ambient temperature for the devices (inside the cabinet /
instal ation box).
Outside, the temperature should be 10 K lower.

5.3.2 Space requirements

Bill of quantity
Space requirements in the installation box can be calculated as follows: • Number of I/O modules x 64 mm. • Number of power modules x 96 mm. • Number of bus interface modules x 32 mm. • DESIGO PXC3 room automation station x 162 mm. • Transformers • Terminal strips. Observe free space!
Al connection terminals must be connected unhindered and inspected. We recommend at least 30 mm between the modules and the cable ducts. This results in the following distance of the standard rails/cable ducts: 90 mm (module width) + (b = cable duct width) + 2 x ≥30 mm (available space for Mounting and installation Building Technologies Installation box TRA 5.4 EMC compliant instal ation box

One duty of the installation box is to reduces electromagnetic interference. The influence depends on the internal and/or external EMC disturbances of the
installation box. The internal EMC disturbance can be, for example, an inverter in the same installation box; an external disturbance a nearby RF transmitter. The installation boxes are the reference point for shielding cables and housings. They must decouple faults and short-circuit surges. General rules
The following generally applicable rules apply to an EMC compliant installation box: Installation box • Interior walls cannot be painted if difficult EMC conditions prevail. mechanical design • Grates and rails must be conductive and may not be painted. • Screws are attached directly on blank areas in the installation box. • Grounding connections with doors through flat copper banks (eventually including a connection to normal protective grounds). Strongly disruptive devices must be separated as far as possible from victim when setting up the installation box. Special attention must be placed on the connections between the two device groups: • Use separate installation boxes for strong disturbances and victims. • Place stronger source of disturbances outside the installation box. Do not violate safety requirements. • Separate the device groups within the installation box with a separating plate. • Cable screens must be installed as close as possible to the installation box insert on its metal structure and connected to the building's potential • Screen connection terminals must be used and suitable installation space be provided to this end (see drawing on P Exception
Using screens to power the TX-I/O modules: See TX-I/O engineering and installation, CM110562. Mounting and installation Building Technologies Installation box TRA 5.5 EMC compliant wiring

Wiring rules
If heavy EMC disturbance is expected in an installation box or in the building, the following wiring rules can better protect potential victims: Installation box wiring
• In the installation box, separate unshielded lines from shielded lines at the terminal connections and cable ducts. • Avoid cable loops. • Plan sufficient space to correctly connect the cable screens. • Connect cable screens to the installation box directly at the inlet to the installation box. Leave screen intact to the module. • Integrate the installation box with the building's potential equalization. Building wiring
Different types of cable When setting up cable ducts, separate strongly disruptive cables from victims. in one cable duct. • Disruptive cable: Motor cables, energy cables. • Possible victims: Control cables, low-voltage cables, interface cables, LAN cables, digital and analog signal cables. • Both types of cables may be in the same cable duct, but should be place is separate compartments. • If not three-sided duct with separating wall is available, the disruptive cables must be separated by at least 150 mm from the others or placed in separate • The crossing of strongly disruptive cables should be at a right angle to potential • Comply with the manufacturer's installation recommendations for the selection of shielded or unshielded cables. In general, unshielded twisted pair cables have
sufficient EMC properties for building-technical applications (including data • Unshielded round wires can also be used for the island bus (wire CS, CD).
• Benefit: Unscreened cables do not need to be coupled to the surrounding Screening improves EMC properties. Please note the following, however: • The grounding (common reference point), is tasked with diverting and short circuiting existing interference voltage. • Special emphasis must be placed on the grounding concept to prevent grounding loops or differences in potential○. • Against low-frequency interference: Ground the screen on one side only. • Screens must be connected on both sides with the ground against high frequencies. Potential equalization must never take place via the cable screens. A separate potential equalization must be installed when missing. Alternative: hard wired earthing on one side, via a capacitor on the other side. • The cable screens must be properly connected to the ground to achieve a solid level of screening (see below). • Island bus extension, see: TX-I/O engineering and installation, CM110562) Mounting and installation Building Technologies Installation box TRA Attaching cables to the
Strain releaf of cables is done on the outside of the installation box. installation box
Attaching cables in the
Cable screens for screened wiring must be installed as close as possible to the cabinet inlet on its metal structure and connected to the building's potential equalization. The following il ustrations display the correct connections for shielded and unshielded cables to the screen and cable fastening rails. Use only off-the-shelf screen terminal connections for trouble-free screen Attaching cables in the cabinet
Run screening to the module, but do not connect it to the module! Cable fastening rails Screen connection Cable unscreened The screen rail cannot be used to relieve cable strain. Screen connection with screen connection terminals
Screen connection terminals Screen rail support rail Avoid screen braid. Mounting and installation Building Technologies Installation box TRA Wiring of field devices (without bus)
As a rule, comply with local regulations for electrical installations.
These take precedence over any notes in this document.

6.1 Power lines AC 230 V
The sizing and fusing of the power lines are oriented to overall load and local
6.2 Wiring for Triac outputs AC 24 V
The following applies for wiring to actuating devices such as valves, damper actuators or protection connected to the Triac outputs: • Use stranded, 2 or multiple core round cables, screened (standard off-the-shelf installation cable). • Single wires may not be used. • Wiring may be laid together with power lines (AC 230 V). They must be isolated from the power lines per regulations. Isolation must meet PELV requirements. • Wiring can not be led in the same cable as the power lines. • See table below for maximum single cable lengths. However, the length must not exceed 300 m (EM interference).
• Use cable cross section suited for 10 A according to local regulations Caution!
(T 10A fuse in the power supply module / room automation station). Cable designation A R
Cable length Lmax [m]
Outgoing and return
cables may each have the
indicated length!
AWG [mm2] [mm] [Ohm/km] VA
Mounting and installation Building Technologies Wiring of field devices (without bus) 6.3 Signal wiring
The following applies in common for signal wiring of field devices such as temperature sensors, window switches, presence detectors, dew point sensors or electrical buttons: • Use stranded, 2 or multiple core round cables, without screen (standard off-the- shelf installation cable). • Single wires or ribbon cables may not be used. • Signal wiring may be laid together with power lines (AC 230 V). They must be isolated from the power lines per regulations. Isolation must meet PELV requirements. • Signal wiring can not be led in the same cable as the power lines. • The length must not exceed 300 m (measuring errors, EM interference). • In case of active sensors with AC 24 V supply, use cable cross section suited for Caution!
10 A according to local regulations (T 10A fuse in the power supply module / room automation station).
6.4 Relay outputs
The following applies for the 230 V wiring: • The maximum load of the relay contracts must be observed (see data sheets for the corresponding devices) • The sizing and fusing of the power lines are oriented to overall connected load and local regulations. • The fused electrical values must therefore be reviewed in the data sheets for the corresponding devices. • The lines must be secured on the device with strain relief. • Cable length: as per load and local regulations.
RXM39.1 also has a relay contract (Q14) for switching electrical heating coils (see
data sheet N3836). Observe the following: • The maximum power is 1.8 kW ohm load. Larger loads close the contact too • A external fuse of max. 10 A is planned to protect circuits on the PCB of the PL-
TXM1.6RL can switch lighting groups up to 10 A. Fusing max. 16 A.
See data sheet N8177. Mounting and installation Building Technologies Wiring of field devices (without bus) Wiring for AC 24 V and island bus
Before starting the wiring, please comply with in Sectiand the listed below. Detailed information on wiring for AC24V and island bus is available in the TX-I/O engineering and installation guide CM110562 [2].
7.1 Supplemental notes on safety

Safety notes The following notes are closely related to Section
and must be observed accordingly. Cabling,
Wire the devices in the standard manner in the cable ducts. duct cross-section
Recommendation: Design the duct cross-section with at least 30% in reserve. Wiring and connection
Use wiring types and diameters as per the specifications below: terminals
Use standard stranded cable and wiring. The ends can be connected directly or strengthen with conductor sleeves or .Important: If low-voltage wiring runs alongside mains
voltage, it must have the same level of insulation as wiring
for mains voltage. The device connection terminals are designed for wiring for: • min. 0.5 mm ∅. Connection terminals are lifting clams; the contact plate between the wire end and screw end is easy on the wiring. .Important: Only the original pluggable connection
terminals may be used as the connection facility.
Tightening torque
Set the torque to 0.5-0.6 Nm or 50-60 Ncm when using electrical screwdriver on the connection terminals. Mounting and installation Building Technologies Wiring for AC 24 V and island bus 7.2 Wiring for AC 24 V

This section describes the wiring between the transformer and power point(s)
(Room automation station, power module, bus interface module). The following diagram il ustrates basic wiring for power lines for modular room automation stations using AC 24 V operating voltage as per PELV: Installation example
Installation box 1   Installation box 2 Safety transformer AC 230 V / AC 24 V as per EN 61 558. Terminal block for star distribution of AC 24 V and ⊥. DESIGO PXC3 room automation station. Room automation station PXC3, with separate power AC 24 V (looped power from T1 admitted but not recommended). Power supply module TXS1.12F10 Bus interface module TXS1.EF10 Low-voltage fuse, for max. power with AC 24 V. 10 A fuse holder in the PXC3 10 A fuse holder in power module. 10 A fuse holder in the bus interface module. Mounting and installation Building Technologies Wiring for AC 24 V and island bus Secure operation
• The next device has no AC 24 V power when a room automation station is removed. The connection exists only on the board, but not on the terminal block. The Ethernet switch is inactive when a room automation station has no AC 24 V power. The next devices, if in line topology, are disconnected from the network. For secure operation of the system it is recommended to supply each
room automation station separately with AC 24 V.

7.3 Transformer sizing
The AC 24 V is wired in star distribution for one PXC3. room automation station. The AC24V may be looped via terminals 7 and 8 as wel for multiple PXC3. However, 10 A must never be exceeded at AC input terminals 5 and 6.
Possible wiring lengths are half as long at the same power when wired for star distribution. The permissible voltage drop of 0.6 V on the power wire between the transformer and the most distant power point (room automation station, power module, bus interface module) is the basis for calculations. The engineering office is responsible for sizing transformer output. Power consumption
Max. permissible input current AC 24 V
Total max. 10 A
(through terminals 5 and 6)
(Ext. fusing compulsory)
Base load (without loading by modules and field 8 VA / 0.33 A Island bus supply *) The bus supply can be switched off manually via ABT if not used. Factory setting: "Auto detection" Transit power AC 24 V TX-IO: AC 24V / 6 A (island bus) PL-Link: AC 24V / 2 A(terminals 3 and 4) (terminals 7 and 8, for additional AV 24 V (only if the sum of 10 A at terminals 5 and 6 is not Mounting and installation Building Technologies Wiring for AC 24 V and island bus Power consumption TX-I/O: Consumption data DC 24 V per I/O point
(values in mA, for supply sizing) Intrinsic consumption 1) 25 25 35 20 25 25 10
Digital input 2) (contact closed) (Temp. sensors Ni, PT, T1) Analog input 3) (Temperature sensor NTC) Analog input 3) (Resistance) Analog input (10 V) 2) Digital output (relay active) 2) Digital output (triac active) 2) 5) Analog output (10 V) 2) Unconfigured I/O point (Reserve for later configuration) 1) Including module status LED; includes LCD and al override LEDs if applicable 2) Including I/O status LED 3) Included in intrinsic consumption (no I/O status LED for temperature inputs) 5) The triacs have a switch capacity of AC 24 V, 125 / 250 mA (max 500 mA for 90 s).
This power is supplied by the 24 V conductor, not by the DC 24 V power supply. Power consumption of
Typically 5 mA at DC 24 V PL-Link devices
However, check each device's data sheet.
In particular, the QMX3 room unit uses max. 12.4 mA.
Power consumption of
Typically 2 mA at DC 16 V DALI devices
Load-dependent cable
The table below provides permissible loads based on cable lengths and cable cross sections. It is the distance between the transformer and the most distant Permissible load [VA] Cable length for AC 24 V
Cable cross-
Mounting and installation Building Technologies Wiring for AC 24 V and island bus • The supply wire (AC 24 V) and return lines (⊥) can each have the indicated • Power is added together for multiple back-to-back looped stations which reduces the cable length accordingly. • Each supply point (room automation stations/power module/bus interface module) is either connected separately to the transformer's terminal block (star wiring) or looped via the room automation station. • Cables may be wired in parallel to increase the cross section.
In practice, the small level of permissible voltage drop off means that the
transformer must always be instal ed in close proximity to the consumers
and that any cascading powering of room automation stations is only
possible over short distances or at smal outputs.
Mounting and installation Building Technologies Wiring for AC 24 V and island bus 7.4 Island bus wiring

• PXC3 room automation stations each have switchable TX-I/O DC 24 V / 600 mA
module power supply. They are switched on at the factory. • The mounting and installation guide TX-I/O engineering and installation guide 10562 [2] includes detailed information on island bus wiring and island bus extension for PXC3 room automation stations and TX-I/O modules. • Island bus and island bus expansion are designed for indoor use in one building The following diagram displays basic wiring variants of the island bus together with the room automation station:
– TX-I/O modules on the same standard rail as the PXC3.
– TX-I/O modules on a different standard rail, connected via an additional bus
interface modules X1, X2.
– TX-I/O modules on a different standard rail, connected via an additional power
supply module U2.
– TX-I/O modules in an offset installation box; connected via island bus
extension modules U4, U5.
Island bus-Extension PXC3 room automation station. X1, X2 TXS1.EF10Bus interface modules U2, U3 TXS1.12F10Power supply modules U4, U5 TXB1.IBE Island bus extension modules Notes • The bus connection module (X1) must be placed at the end of the TX-I/O row.
Modules to the right side of the bus connection module would otherwise have no supply of AC 24 V. • The island bus extension modules (U4, U5) may be anyplace in their TX-I/O
row. For signal quality reasons, however, the best place is directly after the power supplying device Mounting and installation Building Technologies Wiring for AC 24 V and island bus Ethernet network
8.1 Network topologies

Topologies
You can use the following bus topologies: • Star topology (general). • Line topology (for room automation). Star topology
Line topology
Notes • The number of room automation stations is limited to 20 for a line topology • The next device has no AC 24 V power when a room automation station is removed. The connection exists only on the board, but not on the terminal block. Availability / • The Ethernet switch is inactive when a room automation station has no AC 24 V
reliability
power. The next devices, if in line topology, are disconnected from the network. For secure operation of the system it is recommended to supply each room automation station separately with AC 24 V. Mounting and installation Building Technologies Ethernet network 8.2 Cables

PXC3 room automation stations are connected to one another via switches and
Ethernet cables with RJ45 connectors. The following conditions must be met: Bus cable and length
• Standard Ethernet cable • Shielded or unshielded STP (Shielded Twisted Pair) or UTP (Unshielded Twisted Pair).
• Length between switch and PXC3 • Length between PXC3 devices • Number of devices under a line topology • Standard IT product at 100 MB or 1 GB. Reference documents
Additional information: • Desigo Technical principles manual [3], Section 3 (overview), 16 (network view) and 18 (system limits). • Ethernet, TCP/IP as well as BACnet on Ethernet/IP principles [6]. Mounting and installation Building Technologies Ethernet network PL-Link room bus
• The PL-Link bus facilities communications from the PXC3 room automation station to a maximum 64 PL-Link / KNX bus devices for various manufacturers. • The PL-Link bus basic version comprises one cable and two stranded bus wires. • The PXC3 has one internal bus power supply of 160mA. • The PXC3 also includes an AC 24 V / 2A output for PL-Link / KNX bus devices with increase power consumption that is supplied via AC 24 V rather than via the • The PL-Link is physically based on the KNX bus (Konnex). • In PL-Link networks area/line couplers and IP routers are not admitted. • Interconnection of PXC3 room automation stations via the PL-Link is not admiss- ible; the connection is done exclusively via Ethernet switches (Secti • The polarity of the PL-Link bus conductors must be respected (terminals PL+ and PL–) In most countries, specific /KNX know-how is transmitted through training centers certified by the EIBA (sor
9.1 Bus power supply

A bus power supply is required for bus communications. Throttled voltage DC 29 V
is used.
9.1.1 PXC3 internal PL-Link power supply

The PXC3 room automation station has an internal bus power supply of 29 V / 160 mA. The ABT recognizes if any devices are connected to the PL-Link rail (auto detection) and the PXC3 then switches the power supply on. If an external supply
is used, the internal supply must be switched off manual y in the ABT (PL-
Link rail properties), as parallel operation is not permitted. Bus power and the PL-Link bus are galvanically isolated from device electronics for devices with bus power. Parallel operation not
Parallel operation of the internal PL-Link bus supply with an external bus power permitted
supply is not permitted. The internal bus power supply must be switched off in ABT when an external bus power supply is used. Default = "Auto Detection". Mounting and installation Building Technologies PL-Link room bus 9.1.2 External bus supply

An external bus power supply unit (PSU) is required when the 160mA of the PXC3
is insufficient to cover the power demand of the connected devices.
Power supply units for 160, 320 and 640 mA available in specialty stores. The total
power supply for the devices must be calculated to determine the appropriate size. Comply with the corresponding details in the datasheet. A 640 mA power supply unit suffices for a line featuring 64 bus devices with an average power demand of 10 mA each. Paral el operation
• In principle, parallel operation of external bus supplies is possible. However, check if the specific PSU is allowed to be operated in parallel with other PSUs. Refer to the technical specifications. The recommended new Siemens power supply units (see below) are admitted for parallel operation. • A minimum cable distance is required between two PSU, see section Siemens power supply
We recommend the following Siemens power supply units for PL-Link networks (see links below). • 5WG1 125-1AB02, short designation N125/02
(with integrated throttle). Parallel operation • 5WG1 125-1AB12, short designation N125/12
(with integrated throttle). Parallel operation • 5WG1 125-1AB22, short designation N125/22
(with integrated throttle). Parallel operation • Operating voltage AC 120…230 V, 50…60 Hz • Bus supply output DC 29 V (21…30 V, throttled) Additional information • Product and function description (inserted with each device). • GAMMA Instabus site: • Technical product information: Mounting and installation Building Technologies PL-Link room bus 9.2 Bus topologies
64 bus devices
Up to 64 bus devices can be installed on one line (main line as well). No on one line
restrictions apply to the type mix. • There is no need to calculate the bus load number E for up to 64 devices. • A maximum of 64 devices may be installed even if devices requiring less power Permissible bus topologies are: Tree, line, and star topologies. These topologies can be mixed as needed. However, ring topologies are not allowed. The tree topology is advantageous if a large network must be created. Tree topology (with stub lines) Line topology (with loops) N1 . N7 Bus devices Device with screw terminals T branch with bus terminals Device with spring cage Branching and
connection variants
N1 . N8 Bus devices Mounting and installation Building Technologies PL-Link room bus 9.3 Cables

The bus lines (= wired pair) are connected via PL+ (red) and PL– (black). Bus cable selection Choose the bus cable as per country-specific offerings. Comply with values indicated in this document under "Technical data PL-Link". AC24V can be provided in the same (2 x 2 stands) or in a separate cable. Recommended bus cable are available on the KNX homepage under Downloads / Support – 06 KNX Certification – 02 KNX Certified Products – Cable: Commonly used cable sizes: – 1 x 2 x 0.8 mm (e.g. Belden YE00819 or YE00905). – 2 x 2 x 0.8 mm (e.g. Belden YE00820 or YE00906). Bus cable screening In TRA plants, bus cables without screen are permitted. The screens available for
bus cables do not need to be connected.
If interference is expected on the PL-Link (KNX) bus, use a cable with screen.
Connect the screen as per standard installation rules. The indications for distances and line lengths in a network are designed for bus cables specified by KNX. Network with internal
Comply with the following distances for a PL-Link network with the PXC3 internal PXC3 power supply
power supply: • Distance between bus device and internal supply • Distance between bus devices • Total length of all lines on one line Network with external
Comply with the following distances for a PL-Link network with external bus power power supply
supply (PSU) (see Secti • Distance PSU to PXC3 with switched off internal supply Min. 0 m. • Distance bus device to next PSU • Distance between two PSU operated in parallel Min. 0 m for the new Siemens power supply modules recommended in section Fehler! Verweisquel e konnte nicht gefunden werden..
• Distance between bus devices • Total length of all lines on one line Polarity
Important: The bus conductors must NOT be inverted.
(terminals PL+ and PL–). Mounting and installation Building Technologies PL-Link room bus • At least one supply (internal or external) is required for each line, and max. two supplies (external) are allowed per line. • Install the power supply unit as close to the network center as possible to achieve maximum line size. • The distance between the bus device and the next neighboring PSU may not exceed 350 meters. As a result: Even if the power demand from the bus devices does not require it, two
power units must be used depending on the line length.
Power supply AC 24 V
The PXC3 room automation station also includes an AC24V / 2 A / 48 VA output for PL-Link / KNX bus devices with increased power consumption that is supplied via AC 24V rather than via the PL-Link bus. Voltage drop off between the room automation station and bus devices is maximum -7 % (-1.7 V). The table below provides permissible loads based on cable lengths and cable Permissible load [VA] Cable length for AC 24 V
Cable cross
(diameter)
AWG20 (*)
0.5 mm2 (0.8mm)
AWG18 (*)
0.8 mm2 (1.0mm)
1.3 mm2 (1.3 mm)
2.1 mm2 (1.6mm)

9.4 Commissioning notes

Observer the following commissioning aspects to commission a PL-Link network as
Check the bus wiring prior to commissioning, and make sure that the bus line PL-Link bus
polarity is not interchanged (terminals PL+ and PL–).
Important:
Do not interchange the bus line polarity.
Operating voltage
Check the operating voltage wiring to make sure that the devices are connected to AC 24 V or AC 230 V (as per the technical device information). Apply operating voltage only after this check. Bus power supply
After switching on operating voltage, you must check whether bus power from the PXC3 or the PSU is available. Mounting and installation Building Technologies PL-Link room bus 9.5 Technical data PL-Link

Transmission medium (bus cable) TP (twisted pair) 9.6 kbps (fixed for TP) Bus line polarity PL+, PL– (not interchangeable) Bus terminating resistor Communication signal The communication signal (information) is transferred symmetrically, i.e., as voltage dif erence between the two bus lines (and not as a voltage dif erence to the earthing potential). The sign preceding the voltage between PL+ and PL– determines signal values 0 and 1. PL-Link bus cable 2-wire, stranded (one wire pair) or 2x2-wire, stranded Min. 0.8 mm (AWG20) Max. 1.0 mm (AWG18) 20 … 75 Ω/km Specific capacity 10 …100 nF/km at 10 kHz Specific inductivity 450 …850 µH/km at 10 kHz PXC3 devices do not have a connection for bus cable screens Bus power supply Internal bus power from room automation station PXC3 160 mA from the internal bus power supply is sufficient for max. 32 PL-Link devices with 5 mA each. If the consumption is more than 160 mA (more than 32 devices or more than 5 mA per device), one or two external bus power supplies are required. In this case the internal bus power supply must be disabled via ABT, as parallel operation of the internal supply with external supplies is not admissible. Max. number of devices 64 devices in a PL-Link network. Mounting and installation Building Technologies PL-Link room bus 10 DALI network
• The DALI network allows the PXC3 room automation station to a maximum 64 DALI operational devices. • The DALI network comprises one cable and two stranded bus wires. The mains power may also be available in the same cable (L, N, PE). • The PXC3 possesses a DALI bus supply of 128mA to power up to 64 DALI operational devices. For basic and planning know-how see the DALI manual:
10.1 Bus power supply

A bus power supply is required for bus communications. Power consumption
PXC3 room automation stations each have switchable (via the ABT) bus supply of 16 V / 128 mA. They are switched on at the factory. • Parallel switching with an external power supply is not permitted.
• An external power supply cannot be connected if the internal power supply is • Power consumption of all operational devices on the DALI circuit may not exceed 128 mA (64 x 2 mA). • Bus power and the DALI bus must be galvanically isolated from device electronics for devices with bus power.
10.2 Bus topologies
64 operational devices
Up to 64 DALI operational devices may be installed on one DALI circuit. No in a circuit
restrictions apply to the type mix. Permissible bus topologies are: Tree, line, and star topologies. These topologies can be mixed as needed. However, ring topologies are not allowed. Tree topology (with stub lines) Line topology (with loops) N1 . N7 Operational devices Mounting and installation Building Technologies 10.3 Cables

The bus lines (= wired pair) are connected via DALI (DA). Observe polarity. Bus cable selection Use standard off-the-shelf installation materials to wiring mains power. You must observe the values indicated in this data sheet under "Technical data DALI". AC24V can be provided in the same (2 + 3 stands) or in a separate cable (5 wire). Commonly used cable sizes (as per DIN VDE 0100/T520/Section 6): – NYM 5 x 1.5 mm2 A 1.5 mm2 cable corresponds to a AWG16 cable. Distances
The overall length is 300 meters for a wiring cross-section of at least 1.5 mm2. The permissible voltage drop off over the DALI line and the terminals is a maximum of 2 V. The voltage drop off over the DALI line is typically 90% of 2V (1.8V) and via the terminals 10% of 2V (0.2V). . Regulations
Must comply with low-voltage installation regulations since the DALI signal is not Faulty wiring
NO protection against miswiring with AC 24 V or AC 230 V:
Applying a voltage between DA+ / DA+ or between DA– / DA– wil destroy the
DALI PCB!
This is particularly the case when the AC 24 V supply plug is connected to
the DALI socket.
Mounting and installation Building Technologies 10.4 Technical data DALI

Transmission medium (bus cable) TP (twisted pair) Bus line polarity DA, DA (interchangeable) Bus terminating resistor Communication signal The communication signal (information) is transferred symmetrically, i.e., as voltage dif erence between the two bus lines (and not as a voltage dif erence to the earthing potential). The sign preceding the voltage between DA+ and DA– determines signal values 0 and 1. 2-wire, stranded (one wire pair) 5-wire, stranded 7-wire, stranded Wiring cross section Min. 1.5 mm2 (AWG16). Distance (sum of all bus sections) Note PXC3… devices do not have a connection for bus cable screens. Bus power supply Bus power through the PXC3… room automation DC 16 V, 128 mA. (for max. 64 DALI devices) Mounting and installation Building Technologies 11 EnOcean RF networks
11.1 Technology

(This section is based on the document "EnOcean Range planning" by Engineer Armin Anders, EnOcean LLC). The patented EnOcean RF technology creates a surprisingly far-reaching signal with remarkably little energy. So that devices can be operated trouble-free without solar cells, Piezo elements or thermocouples. The patented EnOcean RF technology creates a surprisingly far-reaching signal with remarkably little energy. So that devices can be operated trouble-free without solar cells (for room temperature sensors) or Piezo elements (switches/buttons). At just 50 µWs, a standard EnOcean RF modules can transmit a signal over a distance of 300 meters (in a free field). The secret is the signal duration is just one one thousandth of a second and triggers, executes and concludes the entire Figure: EnOcean technology uses Summary of EnOcean RF standards
High reliability
• License-free frequency ranges 868 MHz or 315MHz at 1% duty cycle (comply with local law/releases). • Multiple telegram transmission with checksum. • Short telegrams (ca. 1ms) results in a low probability of collisions. • High range: 30 meters in buildings & 300 meters unhindered. • Repeater available for extensions. • Uni and bidirectional communications. Low energy demand.
• High data transmission rate of 125 kbps. • Low "data overhead". • ASK modulation. Mounting and installation Building Technologies EnOcean RF networks • RF protocol is defined and integrated in the modules. • Sensor profiles are established and followed by users. • Unique transmission ID (32 bit). Coexistence with other • No interference with DECT, WLAN, PMR systems, etc.
RF systems
• System design verified in an industrial environment. Specially suited for
• Renovation projects (old buildings, museums, churches, historical buildings, • Rooms where wall reworking is difficult or even impossible (sandstone, glass, • Spaces requiring adjustable room division (open plan offices, museums, TV • Rooms with flexible furnishing or frequently changing decor • System extensions Switches, sensors and actuators in building technology. Wireless range in building is ca. 30 m. For operation with a control unit, the connection to the gateway must first be set up. See data sheet N1661 (Gateway EnOcean/LonWorks) or N1662 (Gateway Typical application (example with additional third-party components) Temperature monitoring Function
Data telegrams from EnOcean devices are received by the receiver (e.g. EnOcean / KNX Gateway) and forwarded as communications objects to the control unit. This type of cooperation requires that the receiver "trained" the sender. See data sheet N1662 (Gateway EnOcean/KNX). Current room device data are sent only every ca. 15 minutes to consume as little energy as possible. However, this signal, a so-called presence signal, is always Mounting and installation Building Technologies EnOcean RF networks sent. Moreover, some events are sent with a ca. 2-minute delay or immediately. For details, see the technical data "Frequency of transmission". The room device stops transmitting if the energy store is not charged sufficiently and/or the battery is empty. 100% functionality cannot be guaranteed under all circumstances. There are simply too many possible sources of interference, both legal and il egal, impacting range tremendously. This includes radio applications using the same frequency for transmission, e.g. other control systems with wireless connection. In addition, reflection based on room design or interior décor impacts signal quality and transmission security. Additional information
Detailed information is available on the EnOcean homepage at: The EnOcean Al iance homepage includes a list of all manufacturers offering compatible devices:
11.2 Lighting conditions at mounting location

This section refers to room units equipped with solar cel s. The data provided
below is based on QAX9x.4 room units.
For guaranteed operation (without battery), at least 200 Lux il uminance must be
present for at least 3 to 4 hours daily. Avoid direct exposure to the sun, as this results in fault temperature readings. Avoid also shading by furniture as well as mounting in wall recesses without sufficient lighting. Startup time at empty energy store: Approx. 1 min. at 400 lx Il umination time required to charge the empty energy Approx. 6 h at 400 lx 1), 2) store for 14 hours operation in total darkness: Il umination time to recharge a working energy store for Approx. 2 h at 200 lx 1), 2) 14 hours operation in total darkness: Maximum operating time at 100% charge and total darkness: 1) Sending a radio signal ca. every 15 minutes (average). 2) Typical value depending on prior charging of energy cell. As brightness is hard to evaluate, we recommend control measurements using a device to measure il uminance. Mounting and installation Building Technologies EnOcean RF networks 11.2.1 Definition: Illuminance

Brightness refers to how the human eye perceives the intensity of a light source. Brightness is measured in Lux [lx]. The human eye can perceive various light sources with the same brightness. Depending on the technology, solar cells have varying degrees of efficiency for daylight and artificial light. Fluorescent lights require at least 30% greater brightness to generate the same level of charging as daylight. The value of the product light (Lux) and duration (h) are referred to as Lux h. The amount of available daylight in the winter is minimal. Winter must be used for calculations if the intent is to guarantee functionality. Of further note is that il uminance dif ers on horizontal versus vertical surfaces. As a matter of principle, horizontal surfaces are better then vertical, of course with the exception of roofs.
11.2.2 Minimum room conditions

The following minimum conditions must be guaranteed for the mounting location of STM solar cel s: • Check the STM initialization parameters as described in the user's guide. • Check light sources (daylight or artificial light). Assume a worst case involving fluorescent lamps if the light source cannot be clearly defined. • Define minimum brightness and duration of il uminance required to ensure • Check lighting conditions on the planned mounting location for the module assuming the least favorable conditions (e.g. in winter). The energy cell drains too mush if the average il uminance drops below the defined, indicated values and transmission ceases. Transmissions resumes automatically as soon as the energy cell is sufficiently charged. The list provides typical il uminance values. Please use a Lux meter to measure A satisfactory Luxmeter is available as of EUR 30.
Building type
Room type
Typical brightness
Class rooms in general Reading rooms, labs PC rooms, working on PCs Manufacturing halls Development, office Labs and inspections Product packaging Mounting and installation Building Technologies EnOcean RF networks First aide, surgery
11.2.3 Notes on mounting location of room units

• Select the best compromise between Il uminance, ventilation locations and aesthetic requirements. • Where possible, install room units opposite windows with the longest daylight • Avoid recesses without sufficient daylight. • With regard to future room use: Select a mounting location where the room unit is not shaded by users (e.g. by moving around furniture). Fig.: Examples for brightness on various locations in a typical office (desk EA = 500 Whether il uminance on the wall is actually 200 lx, depends in large measure on local conditions. We recommend conducting reference measurements using a luxmeter. A device with battery backup can be used is il uminance is insufficient Mounting and installation Building Technologies EnOcean RF networks 11.2.4 Prior to commissioning

Solar energy cells must be charged prior to commissioning (especial y after storage for long periods in darkness prior to initial installation). This occurs automatically as soon as the solar cell is exposed to light. The device is fully operational after 3 to 4 days if the initial charge is not enough. The energy is now sufficient to ensure full functionality even after darkness (even at night or on weekends for up to 90 hours).
11.3 Battery operation

This section refers to room units equipped with solar cells. Normally, ambient light suffices to charge the energy store required to operate the room device. If, however, lighting conditions at the mounting location are insufficient to meet guide values provided in Secti"Lighting conditions at mounting location", insert a battery in the battery holder. This ensures device operation even under unfavorable lighting conditions.
Use a lithium button cell battery (type CR2032).
It is widely available in electrical supply shops. A battery can have a typical battery life of up to 5 years. The battery wil be emptied sooner if the device is operated in total darkness and radio telegrams are transmitted frequently. Battery-supported operation is neither necessary nor recommended if there is suf icient light!
11.4 RF link properties

General information on
In Europe, room devices use frequency 868.3 MHz and 315 Mhz reserved for this "radio signals"
purpose. This frequency may be used for various applications (ISM) with some limitations. If radio signals on this frequency overlap and interfere, data transmission from a room device to a receiver module may temporarily be impaired. The distance of sender and receiver to various interference sources (e.g. audio/video systems, computer) should at least be 50 cm. Check sensitive medical devices using this frequency range in a case-by-case Caution!
Used together with third-
For detailed information, see the description of the radio signal modules available party receivers
for download at: Mounting and installation Building Technologies EnOcean RF networks 11.4.1 RF signals

Radio signal range
A radio signal's strength decreases with distance as it is sent in all directions. In addition, other factors influence the radio signal strength. Below are a few examples of interference and attenuating impact of dif erent Material:
Passage of radio
uncoated glass Brick, pressboards 65.95 % Avoid under all circumstances to metal ical y
screen a room device.
Building materials as well as wall angles in particular influence the radio signal range with the radio link. The greater the angle at which electromagnetic waves hit a wall, the greater signal attenuation. As a result, avoid flat angles and wall niches. Examples:
Radio signal Passage
RIGIPS wal s, dry Brick walls, aerated Ca. 19 m Reinforced concrete Ca. 10 m Geringe Dämpfung wal s Fire protection walls, The radio signal is isolated elevator shafts, stairwells, supply Mounting and installation Building Technologies EnOcean RF networks 11.5 Planning RF networks
11.5.1 RF signal range

Send RF signals are electromagnetic waves, the field strength at the receiver decreases as the distance to the transmitter increases, in other words, the RF rang e is limited. Any materials in the transmission field reduces the range accordingly. RF waves do penetrate walls, but dampen the strength versus pure line of sight.
Reduction in range from walls versus a free field of view:
Material
Reduction in range versus a
free field of view
Wood, gypsum, uncoated glass, without metal Brick, pressboards Reinforced cement Metal, aluminum lamination
The geometric shape of the room
determines the RF range, since transmission is not in the form of rays, but rather requires a certain room volume (ellipsoid with sender Tx and receiver Rx in both focal points). At 30 meter in range, the ellipsoid center diameter is theoretically around 10 meters (868 MHz). Narrow Fig: Narrow hallways with large walls. hallways with large walls are
The antenna setup and the distance from ceilings, floors and walls plays an
important role. Internal antennas typically have better RF properties versus flush- mount receivers. People and objects in the room also reduce range. The generally standard range of "30 meters in buildings" should be viewed in a dif erential manner dues to the numerous influences. Planning for reserves in the range is necessary to achieve a reliable function of the RF system, even under unfavorable Robust and reliable instal ation in buildings is achieved by ensuring
sufficient range reserves.
Practical hints
• > 30 meter for very good conditions: Large free space, optimum antenna
installation and placement. • Planning security with furniture and people in the room, through up to 5
gypsum drywall or 2 brick/aerated concrete: – > 20 meters for transmitters and receivers with solid antenna execution and
> 10 meters for received installed in the room wall or corner. Or small
receives with internal antennas. Also together with switches on or wire antenna near metal. Or narrow hallway. • Vertical through 1-2 room corners depending on fixtures and antenna execution. • Learning by EnOcean devices can greatly increase availability. A receiver can work with multiple, received signals. Mounting and installation Building Technologies EnOcean RF networks 11.5.2 RF signal shielding

Metal surfaces reflect electromagnetic waves, e.g. metal partitions and metal ceilings, massive steel reinforcement in the concrete walls and metal foils from insulation. Creating RF shading in a "silent zone". Individual, thin metal strips have little impact, for example, strips in a gypsum drywall. Metal surfaces
Mounting a transmitter directly on a metal surface (e.g. panel doors, steel door frames) prevent the free transmission of the RF signal. This may impact RF connection or even cause a loss of connection. Functions are only possible as an exception for a device mounted in this manner and cannot be guaranteed Metal partitions
RF technology does work with metal room partitions. The signals are reflects: Metal and concrete walls reflect RF waves. RF waves penetrate to neighboring hallways or rooms through opening, e.g. a wood door or glass partition. The range can be significantly reduced based on the specific local conditions. An additional repeater in the right place is an easy way to provide and alternative RF path. An EnOcean RF signal can be amplified at most two times by a repeater. Factors reducing range
• Metal partitions or hallow walls with insulation on metal foil. • Suspending ceilings with panels made of metal or carbon fibers. • Steel furniture or glass with metal coating. • Mounting the switch on a metal wall (typically results in a loss of 30% in range). • User of metal switch frames (typically results in a loss of 30% in range). Fire protection walls, elevator shafts, stairwells and supply areas should be considered shielding. Solution
You can eliminate shielding by repositioning the transmitter and/or receiver antenna from the silent zone or using a repeater. Mounting and installation Building Technologies EnOcean RF networks 11.5.3 Penetration angle

The angle at which a transmitted signal hits the wall plays an important role. The effective wall strength and thus the dampening of the signal depends on the angle. The signals should run vertical to the walls as much as possible. Avoid wall recesses as much as possible. Solution
Eliminate excessively flat penetration angles by repositioning the transmitter and/or receiver antenna or use a repeater.
11.5.4 Mounting the antenna

Do not mount the receiver antenna or a receiver with internal antenna on the same wall as the transmitter. RF waves are subject to disruptive refraction or reflection near walls. It is better to mount the receiver on the next or opposite wall. The antenna for devices with featuring external antennas should be mounted in a centralized location in the room. Where possible, the antenna should be at least 10 cm from corners or cement ceilings. Avoid RF transmission along wall surfaces (e.g. in a long hallway as The ideal mounting location of the receiver's antenna is a central location in the room. "Magnetic foot antenna" (e.g. Hirschmann MCA 1890 MH) must attach to a large a metal surface as possible to provide a sufficient counter polarity. For example, mounting the antenna on a ventilation duct. Conversely, a "patch antenna" (surface antenna, e.g. HAMA MiniPlanar 38499) must be mounted in a non-metal ceiling or drywall, for example, in a cavity wall socket of the right size (see image below). A patch antenna cannot normally be mounted directly in cement or in direct proximity to metal. One exception is the "metal patch antenna MCA 1890MP" by the Hirschmann company. The flat antenna can be attached discretely Mounting and installation Building Technologies EnOcean RF networks and directly to a metal ceiling. For additional details on selected suitable plugs, please refer to the application note "AN103 External Antennas" by EnOcean. Mounting magnetic foot antenna Mounting patch antenna Then laying the antenna cable it is important not to bend the cable, causing irreparable damage (reduction in performance caused by a change to wave resistance). A "active antenna" is a RF receiver with integrated antenna. It communicates with an actuator unit, for example, via a simply RS485 cable (RS485 Gateway). So that no shielded antenna is required that suffers from reduced performance as the length increases and that can be bent during installation.
11.5.5 Distances from receive to other sources of interference

EnOcean transmitters can be placed next to any transmitter without a problem.
Conversely, the distance from the EnOcean receiver to other transmitters (e.g.
GSM / DECT / Wireless LAN) and high frequency sources of interference (computer, audio and video systems) must be at least 50 cm. The distance of the EnOcean receiver to other high frequency transmitters
should be at least 50 cm.

The transmitter position is non-critical.

Mounting and installation Building Technologies EnOcean RF networks 11.5.6 Repeaters

Repeaters (i.e. amplifiers) can help overcome problems with reception quality. The EnOcean repeater requires no configuring (e.g. self learning). Simply connect to the supply voltage to commission. The Sections on "Shielding" and "Penetration" include il ustration on possible deployment. Post-installation of repeaters should be considered (electrical connection) during planning for unfavorable situations. Too many repeaters is counter-productive (higher costs, collision of telegrams). EnOcean repeaters cannot be cascaded in their "1-level" basic function, previously repeated telegrams wil not be repeated again. Repeaters switchable to 2-level function do allow for cascading via two repeaters. But it should only be used under exceptional building-technical cases.
11.5.7 Field strength measuring equipment

Of -the-shelf field strength measures devices that easily find the best mounting locations for transmitter and receiver. Faulty connection from previously installed devices can also be reviewed. The RF telegrams and disruptive RF signals are displayed in the relevant frequency range. Additional information available at: Mounting and installation Building Technologies EnOcean RF networks 11.6 Range planning

RF range is typically limited by fire protection walls that are considered shielding. Within fire protection areas, light walls or glass partitions with solid RF properties are often used. Avoid metal reinforcement or metalized glass!. The following diagrams il ustrate how to implement a reliable RF plan in three STEP 1: Floor plan and
STEO 2: Draw relevant
• Fire protection walls RF shielding on the floor
Elevator shafts, stairwells and other supply areas Mounting and installation Building Technologies EnOcean RF networks STEP 3: Draw range
• The center of the circle represents the ideal position for RF gateways. This allows for a shield-free connection in all corners of the fire protection section (possible sensor positions). Real-world experience suggests that unfavorable conditions and shortcomings are commonplace. Planning at 10-12 meter radiuses provide a high level of security; against future changes to environmental changes as well (light walls, furniture, personnel in the room, etc.). One meter either way for the gateway position is not an issue due to reserves, even later. A very robust RF system can be achieved by implementing a redundant RF reception path. This can be accomplished by programming neighboring RF gateways for parallel reception of the RF transmitter. Even if careful y planned, the field strength measuring device should be used on site to test ranges. Unfavorable conditions can be improved through more suitable re-positioning of the devices or through the use of a repeater. Mounting and installation Building Technologies EnOcean RF networks 11.7 Troubleshooting

Trouble free operation of the devices is normally guaranteed if you follow all the notes on the selection of mounting locations for transmitters and receivers. The following overview of potential problems may help should problems nevertheless Transmitter is not
Check with EPM100
Possible cause and solution
received
In close proximity to the transmitter Transmitter is not transmitting.
(ca. 20-50 cm distance), the EPM
Check transmitter: Solar-powered 100 does not receive any
transmitter is supplied with sufficient light transmission telegrams.
as applicable (for quick function test, Trigger transmission telegram, the briefly expose the device to daylight or LED HI is unlit on the EPM. under a bright lamp). In close proximity to the receiver
Transmitter mounted beyond the
(ca. 20-50 cm distance), the EPM
receiver range (or the transmitter was
100 does not receive any
removed in the meantime).
transmission telegrams.
Change the mounting location for the Trigger transmitter telegram, the transmitter or receiver, or use repeater. corresponding LO/HI LED is unlit on Comply with notes in Section 1. EPM (HI for flush-mounted receiver, LO for receiver with external antenna).
In close proximity to the receiver
a) Transmitter did not learn or
(ca. 20-50 cm distance), the EPM
incorrectly learned.
100 has solid reception of the
Have receiver self learn the transmitter. transmitter telegram.
b) Receiver is not receiving.
Trigger transmission telegram, the Check receiver, as needed, the receiver LED HI is lit on the EPM. antenna and cabling for antenna cable as Invalid EnOcean telegrams are
a) High-frequency disruptions in the
permanently received.
vicinity of the receiver.
One of the two LO/HI LEDs is Remove sources of interference (PC, continuously lit on EPM 100, but not wireless phone, etc., at least 50 cm from EnOcean receiver).
b) Jammer (continuous transmission).
Eliminate jammer. Mounting and installation Building Technologies EnOcean RF networks Transmitter is
Check with EPM100
Possible cause and solution
occasionally not
In close proximity to the receiver
a) Transmitter is within the limits of
received
antenna (ca. 20-50 cm distance), the the transmitter.
EPM 100 receives transmitter
Move the transmitter or receiver antenna telegram at the limits.
or use a repeater. Comply with notes in Trigger transmission telegram, the corresponding LO/HI LED is unlit on b) Transmitter not installed where
(HI for flush-mount receiver; LO for expected (or incorrectly assigned
receiver with external antenna). Properly assign transmitter.
c) Transmitter mounting location
changes on occasion (e.g. not tightly
attached).
Move the mounting location of the transmitter within the receiver range. In close proximity to the receiver
Receiver is not receiving.
antenna (ca. 20-50 cm distance), the Check receiver, as needed, the receiver
EPM 100 has solid reception of the
antenna and cabling for antenna cable as transmitter telegram.
Invalid EnOcean telegrams are
Jammer exists.
occasionally received.
Eliminate jammer. One of the two LO/HI LEDs is occasionally lit on EPM 100, but not Mounting and installation Building Technologies EnOcean RF networks 11.8 Commissioning RF link

For operation, the connection to the gateway must first be set up. See data sheet N1661 (Gateway EnOcean/LonWorks) or N1662 (Gateway EnOcean/KNX). Send "Init" telegrams
The LEARN button is located on the lower section of the housing below the battery. Press this button to create and immediately send a complete learning telegram. The current switching status of LEARN – pressed – is also transmitted. If the corresponding receiver is being configured, the information helps assign a specific output channel to the sender. This procedure is referred to as "learning". A normal telegram does not initiate this procedure.
Repeat the procedure if you want to assign several output channels to one
Simple function check
The LEARN button allows for a simple function and range test. Make sure the
room device was charged sufficiently prior to testing.
Depending on receiver type and configuration, an LED indicates if the receiver
finds the LEARN button was pressed on a learned room device. No acknowledgement occurs if the telegram is not received completely. Possible causes: Distance too great or unfavorable mounting location with too many interference sources within the radio link. Of -the-shelf field strength measures devices that easily find the best mounting locations for transmitter and receiver. Additional information available at:
11.9 Gateways

Wireless room units together with a gateway (EnOcean/KNX) can be used with all controllers on a PL-Link or KNX network. EnOcean gateways
RXZ97.1/KNX S55842-Z101 Gateway EnOcean/KNX Engineering KNX
See description of the gateway datasheet [12]. LONWORKS page
Mounting and installation Building Technologies EnOcean RF networks 12 Disposal
The devices are considered electronics devices for disposal in terms of European Directive 2002/96/EC (WEEE) and may not be disposed of as Dispose of the devices via the proper channels. Follow all local and currently applicable laws and regulations. Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division Tel. +41 41-724 24 24 2012 Siemens Switzerland Ltd Subject to change Mounting and installation Building Technologies

Source: http://ibt.su/CM111043en.pdf

Microsoft word - technical specs chapt 7 pass process

PASS CR (MICRO Type II) CAPE SEAL and PASS QB Rejuvenating Seal for Residential Roads SECTION 700 - PASS CR Scrub Seal The work shall consist of furnishing all necessary labor, materials and equipment for the transporting, application of the polymer modified asphaltic emulsion PASS or equal, ¼" by No. 10 premium aggregate to conform to the Provisions of Section 37-2, of the Standard Specifications, Plans and these Special Provisions. The work shall be done in the following order: preparing the pavement surface; applying the emulsion; scrubbing the applied emulsion with an emulsion broom; applying premium aggregate; rolling the ¼" by No. 10 premium aggregate; and sweeping up excess aggregate and more fully described below.

Do any of the medications that i am taking affect my eyes?

Education in the Round My Vision is Blurry: Could it be from any of the medications that I am taking? Mark T. Dunbar, OD, FAAO Director of Optometry Bascom Palme Eye Institute University of Miami, Miller School of Medicine Miami, FL 33136 Mark Dunbar: Disclosure • Consultant for Allergan • Optometry Advisory Board for: