Desigo tra mounting and installation
PL-Link devices QMX3.
Desigo™ TRA
Mounting and installation
Building Technologies
Contents
Mounting and installation
Building Technologies
Mounting and installation
Building Technologies
About this document
1.1 Revision history
Revision Date
Section Page
•
Wiring of field devices
•
External KNX bus power supply
• Gamma Instabus Documentation
• External bus supply types
1.2 Reference documents
Document title
Document
TX-I/O™ Functions and operation.
TX-I/O™ Engineering and installation manual.
Desigo Technical principles manual, Section 21.
Ethernet, TCP/IP as well as BACnet on Ethernet/IP principles
TX-I/O™ Product range overview.
TX-I/O™ Module datasheets.
Data sheet TX-I/O™ supply module and bus interface module.
Data sheet Room units EnOcean QAX9x.4.
Data sheet Room units EnOcean QAX95.1, QAX96.1.
Data sheet Gateway EnOcean/KNX
Desigo PX Mounting and installation guide
Data sheet PXC3. Room automation station
Data sheet RXM21.1 PL-Link I/O Block
Data sheet RXM39.1 PL-Link I/O Block
Gamma Instabus documentation:
Mounting and installation
Building Technologies
About this document
1.3 Before you start
1.3.1 Trademarks
The table below lists the third-party trademarks used in this document and their
legal owners. The use of trademarks is subject to international and domestic
provisions of the law.
Trademarks
Legal owner
American National Standard (ANSI/ASHRAE 135-
Konnex Association, B - 1831 Brussels-Diegem
EnOcean LLC, Germany 82041 Oberhaching
ZVEI - Zentralverband Elektrotechnik- und
Elektronikindustrie e.V., Stresemannallee 19,
D-60596 Frankfurt am Main
Al product names listed in the table are registered (®) or not registered (™)
trademarks of the owner listed in the table. We forgo the labeling (e.g. using the
symbols ® and ™) of trademarks for the purposes of legibility based on the
reference in this section.
1.3.2 Copyright
This document may be duplicated and distributed only with the express permission
of Siemens, and may be passed on only to authorized persons or companies with
the required technical knowledge.
1.3.3 Quality assurance
These documents were prepared with great care.
• The contents of all documents are checked at regular intervals.
• Al necessary corrections are included in subsequent versions.
• Documents are automatical y amended as a consequence of modifications and
corrections to the products described.
Please make sure that you are aware of the latest document revision date.
If you find any lack of clarity while using this document, or if you have any criticisms
or suggestions, please contact your local POC at the nearest branch office.
Addresses for Siemens RCs are available at
Mounting and installation
Building Technologies
About this document
1.3.4 Document use/ request to the reader
Before using our products, it is important that you read the documents supplied
with or ordered at the same time as the products (equipment, applications, tools
etc.) carefully and in full.
We assume that persons using our products and documents are authorized and
properly trained and have the requisite technical knowledge to use our products as
Additional information on products and applications is available:
• On the intranet (for Siemens employees only) at
• At your next Siemens branch officor at your system
• From the support team in the headquarters
if no local POC is available.
Siemens assumes no liability to the extent allowed under the law for any losses
resulting from a failure to comply with the aforementioned points or for the improper
compliance of the same.
1.4 Document validity
Mounting and installation
Building Technologies
About this document
Introdution
2.1 About this document
Main target audience
The mounting and installation guide is targeted at
•
Panel builders and factory instal ers
•
Electricians
•
Engineers
The mounting and installation guide provides all the information needed by the
aforementioned personnel for:
The proper mounting and wiring of Desigo TRA in the instal ation box and
connections to the plant.
An overview of the room automation station product range and its design is
provided for general understanding.
Additional use
The mounting and installation guide is provided to internal engineering personnel at
Siemens Building Technologies and system houses with information on the
following topics:
– Installation variants for room automation station.
– Regulations and notes.
The mounting and installation guide includes all documentation in the form of text
and images required fort he aforementioned target groups and intended use.
It does not include information of plant-specific mounting and wiring work. This
information is available in the appropriate project documentation.
Mounting and installation
Building Technologies
2.2 What does this document describe?
Overview
The document describes proper mounting and wiring for
– the room automation station.
– the TX-I/O modules in an installation box or panel.
– for peripheral devices connected to the TX-I/O modules.
– for peripheral devices connected via PL-Link, DALI and EnOcean.
Topology
PL-Link devices QMX3.
The areas indicated above can be briefly described as follows:
Brief description
Installation boxes.
The following devices are installed in the installation box:
– PXC3. room automation station.
– TX-I/O modules connected to the room automation
station via the island bus.
Building services
Connected plants and systems, including: Heating,
ventilation and air conditioning plants, electrical systems,
etc., as well as electrical areas (switches, buttons, lighting
groups, blinds).
Mounting and installation
Building Technologies
Connections
In general the following connections exist from and to the installation box:
•
Ethernet
Room automation stations as well as Desigo Insight and the primary plant level
PX are connected via Ethernet cables and switches.
•
Island bus / island bus expansion:
A bus cable runs from the room automation station to the external I/O modules.
•
Wiring form I/O modules to field devices (sensors, switches/buttons, control
values, motors, etc).
•
PL-Link
A bus cable runs from the automation station to the PL-Link/KNX devices.
A bus cable runs from the automation station to DALI devices.
The room automation station includes an USB Device interface. It serves for
commissioning and service. ABT and SSA can communicate with the PXC3.
via this interface. Furthermore, access to other PXC3. via the network is
possible. Al testing and commissioning functions including download, online test
etc. are available. For details see SSA (Setup & Service Assistant) Commissio-
•
Wireless connections:
A KNX gateway integrates wireless EnOcean devices (room units, sensors,
Mounting and installation
Building Technologies
Important information on safety
Please comply with This section deals with general and system-specific regulations. It includes
these notes important information for your safety and the safety of the entire plant.
Sections flagged with the warning symbol to the left contain safety-related
Safety notes
requirements and restrictions that must be adhered to at all times to prevent
physical injury and equipment damage.
Please comply with the following general regulations during engineering and
. General
Regulations
execution: • Electrical and mains power ordinances for the given country.
• Other applicable, national regulations.
• Building instal ation regulations for the given country.
• Regulations of the facility supplying electricity.
• Diagrams, cable lists, dispositions, specifications and orders by the customer or
authorized engineering office.
• Third-party regulations, e.g. by the general contractor or building owner.
3.1 System-specific regulations
The electrical safety for building automation and control systems by Siemens
Building Technologies is essentially based on
safely separating low voltage from
mains voltage.
SELV, PELV
Application as per SELV or PELV pursuant to HD 384 "Electrical installation of
buildings" depending on the grounding (⊥ AC24V) of the low voltage:
Ungrounded = Safety Extra-Low Voltage (SELV).
Grounded = Protection by Extra Low Voltage (PELV).
Device-related safety is guaranteed, among others, by
. Device safety
– Low-voltage power supply AC 24 V per SELV or PELV
– Double insulation between mains voltage AC 230 V and SELV/PELV circuits and
Comply with specific regulations for electrical wiring per the following sections.
. Grounding of ⊥
Observe the following points when grounding ⊥ AC 24 V (system neutral):
• Operating voltage of AC 24 V is permitted in principle for both grounded as well
(System neutral)
as non-grounded system neutral. Local regulations and customers apply
• Grounding may be required or not allowed for functional reasons.
Recommendation on
•
AC 24 V systems are general y grounds unless otherwise not recommended
by the manufacturer.
• In order to avoid ground loops, connect systems with PELV to the ground at one
location only (especially for transformers), if no other indication exists.
Mounting and installation
Building Technologies
Important information on safety
The following regulations apply to mains and operating voltage:
. Mains and operating
Regulations
Operating voltage It must meet requirements for SELV or PELV. Permitted
deviation for nominal voltage AC 24 V on the device: -10 - +
• Use safety insulating transformers as per EN 61558 with
double insulation designed for 100% duty to supply
SELV or PELV circuits.
• Power taken from the transformer should be at least 50%
of nominal load for efficiency reasons (effectiveness).
• Transformer nominal power should be at least 25 VA. For
smal er transformers, the ratio of open circuit voltage to
full load is unfavorable
Transformers on the secondary side correspond to the
actual load of all connected devices as per transformer
– AC 24 V line (system potential) must always be fused.
– We required, an additional line ⊥ (system neutral).
Transformer, primary side:
Installation box fuse (control circuit fuse).
. Caution with regard
Any insertion or drawing of dangerous voltages to the system's low-voltage circuit,
to foreign voltages!
e.g. caused by improper wiring directly places people at risk can may result in the
partial or complete destruction of the building automation and control system!
Al wiring existing the building is at severe risk of over-voltage caused by
. Measures against
lightening
atmospheric discharges (lightening). Overvoltages can be inductively, capacitive or
galvanically into electronic systems and may cause faults or even destroy sensitive
components. This overvoltage must be diverted to the earth to limit the damage. This may be
achieved with the help of gas-fil ed surge arrestors, varistors and diodes as well as
capacitors and chokes. Specialized companies (e.g. Siemens, Phoenix) combines these elements into
protective components to provide optimum protection for various systems.
Mains filter
Spikes and high-frequency interference may occur in areas with high levels of
interference. The disturbances not only impact the transformer on the primary side,
but may also influence secondary connected components. A mains filter should be attached on the primary transformer if such interference is
anticipated. Mains filters should be installed as close to the network transformer as
possible and grounded.
Mounting and installation
Building Technologies
Important information on safety
Emergency intervention
Peak loads occur when switching inductive loads that may cause faults to the
of power components
system. In addition, sparks may damage switching contacts. Power components
must include effective protection against disturbances to prevent such faults.
Inductivity (transformers, fuses, relays) are wired directly at the terminals using
transzorbs, MOVs (metalloxyd varistors) or RC elements. The breakdown voltage
of the transzorbs or MOVs must equate to the 1.7 to 2 times the applicable nominal
voltage. Inductive DC consumers can also be suppressed using diodes or RC elements. The transzorbs, MOVs, diodes or RC elements must be optimally matched to the
power components and mounted using short wiring.
3.2 Device-specific regulations
. Field device
connection
Devices using different
Devices must have the required insulation of the power circuits from each other to
be able to connect them directly without additional insulation.
Interfaces for different
Connections via interfaces increase the risk of distributing dangerous voltage
voltage circuits
through the building. Ensure that the required insulation is available at all times and
instal ed per applicable regulations.
The supply terminals of the PXC3. (terminals 7 and 8) bare a max current of
10 A, otherwise the pins get too warm.
An external T10 A fuse is compulsory
Mounting and installation
Building Technologies
Important information on safety
The il ustration is a diagram of a PXC3 room automation station in an installation
box / panel, the TX-I/O modules, connections to the field devices as well as bus
connections (Ethernet, PL-Link, DALI).
Installation box /
Transformer AC 230 V / AC 24 V
PXC3. room automation station.
U1, U3 TXS1.EF10Bus connection modules
I/O row, supplied by the PXC3.
I/O row supplied by a TXS1.EF10Bus connection module
TXA1.IBE Island bus expansion module (optional)
Mounting and installation
Building Technologies
Installation box TRA
5.1 Instal ation box requirements
Please comply with Please read Sections 5.1 "Installation box requirements" and 5.2 "EMC compliant
these notes panel" in the TX-I/O engineering and installation guide [2] prior to engineering and
executing the installation box.
Space requirements
Observer the following for mounting and installation. – Installation depth
– Maintain sufficient cable distance to be able to easily snap on and remove the
screw terminal blocks, even if the automation stations are mounted.
– Room automation stations can be mounted directly next to one another; a
distance of ca. 2 cm is recommended, however, for facilitate access.
– Reserve sufficient free space for subsequent extensions.
Installation mode
The room automation stations and TX-I/O modules are designed for installation on
standard rails (prerequisite to establishing the island bus connection using TX-I/O
Permissible standard rails:
• Top hat rails TH35-7.5 as per EN60715 (35 x 7.5 mm).
• Other top hat rails that meet the following conditions:
– Material thickness exterior max. 1 mm, min. 3 mm in depth
– Internal opening at least 25 mm.
The room automation station may also be attached to a wall if used without TX-I/O
Mounting and installation
Building Technologies
Installation box TRA
5.2 Installation box layout
The table below provides information on general instal ation box requirements.
Check to ensure the individual requirements are met.
Construction, stability and sealing meet applicable
regulations at the plant's location.
• Desigo TRA is designed for an ambient temperature
of -5 - 50°C. PXC3.: 45°C for certain mounting
positions, see below.
Please make sure that the installation box is
sufficiently ventilated to ensure compliance with the
ambient temperature for all devices.
• For devices, the permissible values as per the data
in "Technical data" in the datasheet must be
observed with regard to:
– Humidity, vibration.
– Device IP class and device protective type.
EMC compliant The instal ation box corresponds to the rules described
installation box in Secti
Mechanical dimensions
The following help to determine the required installation box dimensions: – Data on placement in this section.
– Device dimensions in the datasheets [8].
5.3 Geometric design
5.3.1 Mounting position
TX-I/O devices can be mounted in any position:
Recommended
Permissible
• Wall, horizontal from left to right
or from right to left
• On a horizontal surface.
• Wall, vertical from top to bottom
or from bottom to top.
Ambient temperature -5. 50 °C
Ambient temperature -5. 50 °C
For the
PXC3. , the following
restrictions apply:
Recommended
With restrictions *)
• Wall, horizontal from left to right
or from right to left
• On a horizontal surface.
• Wall, vertical from bottom to top.
• Wall, vertical from top to bottom.
Ambient temperature -5. 50 °C
Ambient temperature -5. 45 °C *)
*) 50°C is admissible if the bus supplies use max. 2/3 of the specified load: PL-
Link 105mA, DALI 85mA and island bus 400mA.
Mounting and installation
Building Technologies
Installation box TRA
Note
You must ensure, however, that sufficient ventilation is available to maintain
the permissible ambient temperature for the devices (inside the cabinet /
instal ation box).
Outside, the temperature should be 10 K lower.
5.3.2 Space requirements
Bill of quantity
Space requirements in the installation box can be calculated as follows: • Number of I/O modules x 64 mm.
• Number of power modules x 96 mm.
• Number of bus interface modules x 32 mm.
• DESIGO PXC3 room automation station x 162 mm.
• Transformers
• Terminal strips.
Observe free space!
Al connection terminals must be connected unhindered and inspected. We
recommend at least 30 mm between the modules and the cable ducts.
This results in the following distance of the standard rails/cable ducts:
90 mm (module width) + (b = cable duct width) + 2 x ≥30 mm (available space for
Mounting and installation
Building Technologies
Installation box TRA
5.4 EMC compliant instal ation box
One duty of the installation box is to reduces electromagnetic interference. The
influence depends on the
internal and/or
external EMC disturbances of the
installation box. The internal EMC disturbance can be, for example, an inverter in the same
installation box; an external disturbance a nearby RF transmitter.
The installation boxes are the reference point for shielding cables and housings.
They must decouple faults and short-circuit surges.
General rules
The following generally applicable rules apply to an EMC compliant installation box:
Installation box
• Interior walls cannot be painted if difficult EMC conditions prevail.
mechanical design
• Grates and rails must be conductive and may not be painted.
• Screws are attached directly on blank areas in the installation box.
• Grounding connections with doors through flat copper banks (eventually
including a connection to normal protective grounds).
Strongly disruptive devices must be separated as far as possible from victim when
setting up the installation box. Special attention must be placed on the connections
between the two device groups: • Use separate installation boxes for strong disturbances and victims.
• Place stronger source of disturbances outside the installation box. Do not violate
safety requirements.
• Separate the device groups within the installation box with a separating plate.
• Cable screens must be installed as close as possible to the installation box
insert on its metal structure and connected to the building's potential
• Screen connection terminals must be used and suitable installation space be
provided to this end
(see drawing on P
Exception
Using screens to power the TX-I/O modules: See TX-I/O engineering and
installation, CM110562.
Mounting and installation
Building Technologies
Installation box TRA
5.5 EMC compliant wiring
Wiring rules
If heavy EMC disturbance is expected in an installation box or in the building, the
following wiring rules can better protect potential victims:
Installation box wiring
• In the installation box, separate unshielded lines from shielded lines at the
terminal connections and cable ducts.
• Avoid cable loops.
• Plan sufficient space to correctly connect the cable screens.
• Connect cable screens to the installation box directly at the inlet to the
installation box. Leave screen intact to the module.
• Integrate the installation box with the building's potential equalization.
Building wiring
Different types of cable
When setting up cable ducts, separate strongly disruptive cables from victims.
in one cable duct.
• Disruptive cable:
Motor cables, energy cables.
• Possible victims: Control cables, low-voltage cables, interface cables,
LAN cables, digital and analog signal cables.
• Both types of cables may be in the same cable duct, but should be place is
separate compartments.
• If not three-sided duct with separating wall is available, the disruptive cables
must be separated by at least 150 mm from the others or placed in separate
• The crossing of strongly disruptive cables should be at a right angle to potential
• Comply with the manufacturer's installation recommendations for the selection of
shielded or unshielded cables. In general,
unshielded twisted pair cables have
sufficient EMC properties for building-technical applications (including data
• Unshielded round wires can also be used for the
island bus (wire CS, CD).
• Benefit: Unscreened cables do not need to be coupled to the surrounding
Screening improves EMC properties. Please note the following, however: • The grounding (common reference point), is tasked with diverting and short
circuiting existing interference voltage.
• Special emphasis must be placed on the grounding concept to prevent
grounding loops or differences in potential○.
• Against low-frequency interference: Ground the screen on one side only.
• Screens must be connected on both sides with the ground against high
frequencies. Potential equalization must never take place via the cable screens.
A separate potential equalization must be installed when missing.
Alternative: hard wired earthing on one side, via a capacitor on the other side.
• The cable screens must be properly connected to the ground to achieve a solid
level of screening (see below).
• Island bus extension, see: TX-I/O engineering and installation, CM110562)
Mounting and installation
Building Technologies
Installation box TRA
Attaching cables to the
Strain releaf of cables is done on the outside of the installation box.
installation box
Attaching cables in the
Cable screens for screened wiring must be installed as close as possible to the
cabinet inlet on its metal structure and connected to the building's potential
equalization. The following il ustrations display the correct connections for shielded and
unshielded cables to the screen and cable fastening rails.
Use only off-the-shelf screen terminal connections for trouble-free screen
Attaching cables in the cabinet
Run screening to the
module, but do not
connect it to the module!
Cable fastening rails
Screen connection
Cable unscreened
The screen rail cannot be used to relieve cable strain.
Screen connection with screen connection terminals
Screen connection terminals
Screen rail support rail
Avoid screen braid.
Mounting and installation
Building Technologies
Installation box TRA
Wiring of field devices (without bus)
As a rule, comply with local regulations for electrical installations.
These take precedence over any notes in this document.
6.1 Power lines AC 230 V
The sizing and fusing of the power lines are oriented to overall load and local
6.2 Wiring for Triac outputs AC 24 V
The following applies for wiring to actuating devices such as valves, damper
actuators or protection connected to the Triac outputs: • Use stranded, 2 or multiple core round cables, screened (standard off-the-shelf
installation cable).
• Single wires may not be used.
• Wiring may be laid together with power lines (AC 230 V).
They must be isolated from the power lines per regulations. Isolation must meet
PELV requirements.
• Wiring can not be led in the same cable as the power lines.
• See table below for maximum single cable lengths.
However, the length must not exceed 300 m (EM interference).
• Use cable cross section suited for 10 A according to local regulations
Caution!
(T 10A fuse in the power supply module / room automation station).
Cable designation A ∅
R
Cable length Lmax [m]
Outgoing and return
cables may each have the
indicated length!
AWG [mm2] [mm] [Ohm/km]
VA
Mounting and installation
Building Technologies
Wiring of field devices (without bus)
6.3 Signal wiring
The following applies in common for signal wiring of field devices such as
temperature sensors, window switches, presence detectors, dew point sensors or
electrical buttons: • Use stranded, 2 or multiple core round cables, without screen (standard off-the-
shelf installation cable).
• Single wires or ribbon cables may not be used.
• Signal wiring may be laid together with power lines (AC 230 V).
They must be isolated from the power lines per regulations. Isolation must meet
PELV requirements.
• Signal wiring can
not be led in the same cable as the power lines.
• The length must not exceed 300 m (measuring errors, EM interference).
• In case of active sensors with AC 24 V supply, use cable cross section suited for
Caution!
10 A according to local regulations (T 10A fuse in the power supply module /
room automation station).
6.4 Relay outputs
The following applies for the 230 V wiring: • The maximum load of the relay contracts must be observed (see data sheets for
the corresponding devices)
• The sizing and fusing of the power lines are oriented to overall connected load
and local regulations.
• The fused electrical values must therefore be reviewed in the data sheets for the
corresponding devices.
• The lines must be secured on the device with strain relief.
• Cable length: as per load and local regulations.
RXM39.1 also has a relay contract (Q14) for switching electrical heating coils (see
data sheet N3836). Observe the following: • The maximum power is 1.8 kW ohm load. Larger loads close the contact too
• A external fuse of max. 10 A is planned to protect circuits on the PCB of the PL-
TXM1.6RL can switch lighting groups up to 10 A. Fusing max. 16 A.
See data sheet N8177.
Mounting and installation
Building Technologies
Wiring of field devices (without bus)
Wiring for AC 24 V and island bus
Before starting the wiring, please comply with in
Sectiand the listed below.
Detailed information on wiring for AC24V and island bus is available in the TX-I/O
engineering and installation guide CM110562 [2].
7.1 Supplemental notes on safety
Safety notes The following notes are closely related to Section
and must be observed accordingly.
Cabling,
Wire the devices in the standard manner in the cable ducts.
duct cross-section
Recommendation: Design the duct cross-section with at least 30% in reserve.
Wiring and connection
Use wiring types and diameters as per the specifications below:
terminals
Use standard stranded cable and wiring. The ends can be
connected directly or strengthen with conductor sleeves or
.
Important: If
low-voltage wiring runs alongside
mains
voltage, it must have the
same level of insulation as wiring
for mains voltage.
The device connection terminals are designed for wiring for:
• min. 0.5 mm ∅.
Connection terminals are lifting clams; the contact plate
between the wire end and screw end is easy on the wiring.
.
Important: Only the
original pluggable connection
terminals may be used as the connection facility.
Tightening torque
Set the torque to 0.5-0.6 Nm or 50-60 Ncm when using electrical screwdriver on
the connection terminals.
Mounting and installation
Building Technologies
Wiring for AC 24 V and island bus
7.2 Wiring for AC 24 V
This section describes the wiring between the transformer and power point(s)
(Room automation station, power module, bus interface module).
The following diagram il ustrates basic wiring for power lines for modular room
automation stations using AC 24 V operating voltage as per PELV:
Installation example
Installation box 1 Installation box 2
Safety transformer AC 230 V / AC 24 V as per EN 61 558.
Terminal block for star distribution of AC 24 V and ⊥.
DESIGO PXC3 room automation station.
Room automation station PXC3, with separate power AC 24 V
(looped power from T1 admitted but not recommended).
Power supply module TXS1.12F10
Bus interface module TXS1.EF10
Low-voltage fuse, for max. power with AC 24 V.
10 A fuse holder in the PXC3
10 A fuse holder in power module.
10 A fuse holder in the bus interface module.
Mounting and installation
Building Technologies
Wiring for AC 24 V and island bus
Secure operation
• The next device has no AC 24 V power when a room automation station is
removed. The connection exists only on the board, but not on the terminal block.
The Ethernet switch is inactive when a room automation station has no AC 24 V
power. The next devices, if in line topology, are disconnected from the network.
For secure operation of the system it is recommended to supply each
room automation station separately with AC 24 V.
7.3 Transformer sizing
The AC 24 V is wired in star distribution for one PXC3. room automation station.
The AC24V may be looped via terminals 7 and 8 as wel for multiple PXC3.
However, 10 A must never be exceeded at AC input terminals 5 and 6.
Possible wiring lengths are half as long at the same power when wired for star
distribution. The permissible voltage drop of 0.6 V on the power wire between the transformer
and the most distant power point (room automation station, power module, bus
interface module) is the basis for calculations.
The engineering office is responsible for sizing transformer output.
Power consumption
Max. permissible input current AC 24 V
Total max. 10 A
(through terminals 5 and 6)
(Ext. fusing compulsory)
Base load (without loading by modules and field 8 VA / 0.33 A
Island bus supply
*) The bus supply can be switched off manually via ABT if not used.
Factory setting: "Auto detection"
Transit power AC 24 V
TX-IO: AC 24V / 6 A (island bus)
PL-Link: AC 24V / 2 A(terminals 3 and 4)
(terminals 7 and 8, for additional AV 24 V (only if the sum of 10 A at
terminals 5 and 6 is not
Mounting and installation
Building Technologies
Wiring for AC 24 V and island bus
Power consumption TX-I/O: Consumption data DC 24 V per I/O point
(values in mA, for supply sizing)
Intrinsic consumption 1)
25 25 35 20 25 25 10
Digital input 2) (contact closed)
(Temp. sensors Ni, PT, T1) Analog input 3)
(Temperature sensor NTC) Analog input 3)
(Resistance) Analog input (10 V) 2)
Digital output (relay active) 2)
Digital output (triac active) 2) 5)
Analog output (10 V) 2)
Unconfigured I/O point
(Reserve for later configuration)
1) Including module status LED; includes LCD and al override LEDs if applicable
2) Including I/O status LED
3) Included in intrinsic consumption (no I/O status LED for temperature inputs)
5) The triacs have a switch capacity of
AC 24 V, 125 / 250 mA (max 500 mA for 90 s).
This power is supplied by the 24 V conductor, not by the DC 24 V power supply.
Power consumption of
Typically 5 mA at DC 24 V
PL-Link devices
However, check each device's data sheet.
In particular, the QMX3 room unit uses max. 12.4 mA.
Power consumption of
Typically 2 mA at DC 16 V
DALI devices
Load-dependent cable
The table below provides permissible loads based on cable lengths and cable
cross sections. It is the distance between the transformer and the most distant
Permissible load [VA]
Cable length for AC 24 V
Cable cross-
Mounting and installation
Building Technologies
Wiring for AC 24 V and island bus
• The supply wire (AC 24 V) and return lines (⊥) can each have the indicated
• Power is added together for multiple back-to-back looped stations which reduces
the cable length accordingly.
• Each supply point (room automation stations/power module/bus interface
module) is either connected separately to the transformer's terminal block (star
wiring) or looped via the room automation station.
• Cables
may be wired in parallel to increase the cross section.
•
In practice, the small level of permissible voltage drop off means that the
transformer must always be instal ed in close proximity to the consumers
and that any cascading powering of room automation stations is only
possible over short distances or at smal outputs.
Mounting and installation
Building Technologies
Wiring for AC 24 V and island bus
7.4 Island bus wiring
• PXC3 room automation stations each have switchable TX-I/O DC 24 V / 600 mA
module power supply. They are switched on at the factory.
• The mounting and installation guide TX-I/O engineering and installation guide
10562 [2] includes detailed information on island bus wiring and island bus
extension for PXC3 room automation stations and TX-I/O modules.
• Island bus and island bus expansion are designed for indoor use in one building
The following diagram displays basic wiring variants of the island bus together with
the room automation station:
– TX-I/O modules on the
same standard rail as the PXC3.
– TX-I/O modules on a different standard rail, connected via an additional
bus
interface modules X1, X2.
– TX-I/O modules on a different standard rail, connected via an additional
power
supply module U2.
– TX-I/O modules in an offset installation box; connected via
island bus
extension modules U4, U5.
Island bus-Extension
PXC3 room automation station.
X1, X2 TXS1.EF10Bus interface modules
U2, U3 TXS1.12F10Power supply modules
U4, U5 TXB1.IBE Island bus extension modules
Notes • The
bus connection module (X1) must be placed at the end of the TX-I/O row.
Modules to the right side of the bus connection module would otherwise have no
supply of AC 24 V.
• The
island bus extension modules (U4, U5) may be anyplace in their TX-I/O
row. For signal quality reasons, however, the best place is directly after the
power supplying device
Mounting and installation
Building Technologies
Wiring for AC 24 V and island bus
Ethernet network
8.1 Network topologies
Topologies
You can use the following bus topologies:
• Star topology (general).
• Line topology (for room automation).
Star topology
Line topology
Notes • The number of room automation stations is limited to 20 for a line topology
• The next device has no AC 24 V power when a room automation station is
removed. The connection exists only on the board, but not on the terminal block.
Availability / • The Ethernet switch is inactive when a room automation station has no AC 24 V
reliability
power. The next devices, if in line topology, are disconnected from the network.
For secure operation of the system it is recommended to supply each room
automation station separately with AC 24 V.
Mounting and installation
Building Technologies
Ethernet network
8.2 Cables
PXC3 room automation stations are connected to one another via switches and
Ethernet cables with RJ45 connectors.
The following conditions must be met:
Bus cable and length
• Standard Ethernet cable
• Shielded or unshielded
STP (
Shielded
Twisted
Pair) or UTP (
Unshielded
Twisted
Pair).
• Length between switch and PXC3
• Length between PXC3 devices
• Number of devices under a line topology
• Standard IT product at 100 MB or 1 GB.
Reference documents
Additional information: • Desigo Technical principles manual [3], Section 3 (overview), 16 (network view)
and 18 (system limits).
• Ethernet, TCP/IP as well as BACnet on Ethernet/IP principles [6].
Mounting and installation
Building Technologies
Ethernet network
PL-Link room bus
• The PL-Link bus facilities communications from the PXC3 room automation
station to a maximum 64 PL-Link / KNX bus devices for various manufacturers.
• The PL-Link bus basic version comprises one cable and two stranded bus wires.
• The PXC3 has one internal bus power supply of 160mA.
• The PXC3 also includes an AC 24 V / 2A output for PL-Link / KNX bus devices
with increase power consumption that is supplied via AC 24 V rather than via the
• The PL-Link is physically based on the KNX bus (Konnex).
• In PL-Link networks area/line couplers and IP routers are not admitted.
• Interconnection of PXC3 room automation stations via the PL-Link is not admiss-
ible; the connection is done exclusively via Ethernet switches (Secti
• The polarity of the PL-Link bus conductors must be respected
(terminals PL+ and PL–)
In most countries, specific /KNX know-how is transmitted through training centers
certified by the EIBA (sor
9.1 Bus power supply
A bus power supply is required for bus communications. Throttled voltage DC 29 V
is used.
9.1.1 PXC3 internal PL-Link power supply
The PXC3 room automation station has an internal bus power supply of 29 V / 160
mA. The ABT recognizes if any devices are connected to the PL-Link rail (auto
detection) and the PXC3 then switches the power supply on.
If an external supply
is used, the internal supply must be switched off manual y in the ABT (PL-
Link rail properties), as parallel operation is not permitted.
Bus power and the PL-Link bus are galvanically isolated from device electronics for
devices with bus power.
Parallel operation not
Parallel operation of the internal PL-Link bus supply with an external bus power
permitted
supply is not permitted. The internal bus power supply must be switched off in ABT when an external bus
power supply is used. Default = "Auto Detection".
Mounting and installation
Building Technologies
PL-Link room bus
9.1.2 External bus supply
An external bus power supply unit (PSU) is required when the 160mA of the PXC3
is insufficient to cover the power demand of the connected devices.
Power supply units for
160, 320 and
640 mA available in specialty stores. The total
power supply for the devices must be calculated to determine the appropriate size.
Comply with the corresponding details in the datasheet. A 640 mA power supply unit suffices for a line featuring 64 bus devices with an
average power demand of 10 mA each.
Paral el operation
• In principle, parallel operation of external bus supplies is possible. However,
check if the specific PSU is allowed to be operated in parallel with other PSUs.
Refer to the technical specifications.
The recommended new Siemens power supply units (see below) are admitted
for parallel operation.
• A minimum cable distance is required between two PSU, see section
Siemens power supply
We recommend the following Siemens power supply units for PL-Link networks
(see links below).
• 5WG1 125-1AB02, short designation N125/
02
(with integrated throttle).
Parallel operation
• 5WG1 125-1AB12, short designation N125/
12
(with integrated throttle).
Parallel operation
• 5WG1 125-1AB22, short designation N125/
22
(with integrated throttle).
Parallel operation
• Operating voltage
AC 120…230 V, 50…60 Hz
• Bus supply output
DC 29 V (21…30 V, throttled)
Additional information
• Product and function description (inserted with each device).
• GAMMA Instabus site:
• Technical product information:
Mounting and installation
Building Technologies
PL-Link room bus
9.2 Bus topologies
64 bus devices
Up to 64 bus devices can be installed on one line (main line as well). No
on one line
restrictions apply to the type mix.
• There is no need to calculate the bus load number E for up to 64 devices.
• A maximum of 64 devices may be installed even if devices requiring less power
Permissible bus topologies are: Tree, line, and star topologies. These topologies
can be mixed as needed. However, ring topologies are not allowed.
The tree topology is advantageous if a large network must be created.
Tree topology (with stub lines)
Line topology (with loops)
N1 . N7 Bus devices
Device with screw terminals
T branch with bus terminals
Device with spring cage
Branching and
connection variants
N1 . N8 Bus devices
Mounting and installation
Building Technologies
PL-Link room bus
9.3 Cables
The bus lines (= wired pair) are connected via PL+ (red) and PL– (black).
Bus cable selection
Choose the bus cable as per country-specific offerings. Comply with values
indicated in this document under "Technical data PL-Link". AC24V can be provided in the same (2 x 2 stands) or in a separate cable. Recommended bus cable are available on the KNX homepage under Downloads /
Support – 06 KNX Certification – 02 KNX Certified Products – Cable:
Commonly used cable sizes: – 1 x 2 x 0.8 mm (e.g. Belden YE00819 or YE00905).
– 2 x 2 x 0.8 mm (e.g. Belden YE00820 or YE00906).
Bus cable screening
In TRA plants, bus cables
without screen are permitted. The screens available for
bus cables do not need to be connected.
If interference is expected on the PL-Link (KNX) bus, use a cable
with screen.
Connect the screen as per standard installation rules.
The indications for distances and line lengths in a network are designed for bus
cables specified by KNX.
Network with internal
Comply with the following distances for a PL-Link network with the PXC3 internal
PXC3 power supply
power supply: • Distance between bus device and internal supply
• Distance between bus devices
• Total length of all lines on one line
Network with external
Comply with the following distances for a PL-Link network with external bus power
power supply
supply (PSU) (see Secti • Distance PSU to PXC3 with switched off internal supply Min. 0 m.
• Distance bus device to next PSU
• Distance between two PSU operated in parallel
Min. 0 m for the new Siemens power supply modules recommended
in section Fehler! Verweisquel e konnte nicht gefunden werden..
• Distance between bus devices
• Total length of all lines on one line
Polarity
Important: The bus conductors must NOT be inverted.
(terminals PL+ and PL–).
Mounting and installation
Building Technologies
PL-Link room bus
• At least one supply (internal or external) is required for each line, and max. two
supplies (external) are allowed per line.
• Install the power supply unit as close to the network center as possible to
achieve maximum line size.
• The distance between the bus device and the next neighboring PSU may not
exceed 350 meters. As a result:
Even if the power demand from the bus devices does not require it, two
power units must be used depending on the line length.
Power supply AC 24 V
The PXC3 room automation station also includes an AC24V / 2 A / 48 VA output for
PL-Link / KNX bus devices with increased power consumption that is supplied via
AC 24V rather than via the PL-Link bus. Voltage drop off between the room automation station and bus devices is maximum
-7 % (-1.7 V). The table below provides permissible loads based on cable lengths and cable
Permissible load [VA]
Cable length for AC 24 V
Cable cross
(diameter)
AWG20 (*)
0.5 mm2 (0.8mm)
AWG18 (*)
0.8 mm2 (1.0mm)
1.3 mm2 (1.3 mm)
2.1 mm2 (1.6mm)
9.4 Commissioning notes
Observer the following commissioning aspects to commission a PL-Link network as
Check the bus wiring prior to commissioning, and make sure that the bus line
PL-Link bus
polarity is not interchanged (terminals PL+ and PL–).
Important:
Do not interchange the bus line polarity.
Operating voltage
Check the operating voltage wiring to make sure that the devices are connected to
AC 24 V or AC 230 V (as per the technical device information). Apply operating
voltage only after this check.
Bus power supply
After switching on operating voltage, you must check whether bus power from the
PXC3 or the PSU is available.
Mounting and installation
Building Technologies
PL-Link room bus
9.5 Technical data PL-Link
Transmission medium (bus cable)
TP (twisted pair)
9.6 kbps (fixed for TP)
Bus line polarity
PL+, PL– (not interchangeable)
Bus terminating resistor
Communication signal
The communication signal (information) is transferred symmetrically, i.e., as
voltage dif erence between the two bus lines (and not as a voltage dif erence to the
earthing potential). The sign preceding the voltage between PL+ and PL–
determines signal values 0 and 1.
PL-Link bus cable
2-wire, stranded (one wire pair)
or 2x2-wire, stranded
Min. 0.8 mm (AWG20)
Max. 1.0 mm (AWG18)
20 … 75 Ω/km
Specific capacity
10 …100 nF/km at 10 kHz
Specific inductivity
450 …850 µH/km at 10 kHz
PXC3 devices do not have a connection for bus cable screens
Bus power supply
Internal bus power from room automation station PXC3
160 mA from the internal bus power supply is sufficient for max. 32 PL-Link devices
with 5 mA each. If the consumption is more than 160 mA (more than 32 devices or more than 5 mA
per device), one or two external bus power supplies are required.
In this case the internal bus power supply must be disabled via ABT, as parallel
operation of the internal supply with external supplies is not admissible.
Max. number of devices
64 devices in a PL-Link network.
Mounting and installation
Building Technologies
PL-Link room bus
10 DALI network
• The DALI network allows the PXC3 room automation station to a maximum 64
DALI operational devices.
• The DALI network comprises one cable and two stranded bus wires. The mains
power may also be available in the same cable (L, N, PE).
• The PXC3 possesses a DALI bus supply of 128mA to power up to 64 DALI
operational devices.
For basic and planning know-how see the DALI manual:
10.1 Bus power supply
A bus power supply is required for bus communications.
Power consumption
PXC3 room automation stations each have switchable (via the ABT) bus supply of
16 V / 128 mA. They are switched on at the factory.
• Parallel switching with an external power supply is
not permitted.
• An external power supply cannot be connected if the internal power supply is
• Power consumption of all operational devices on the DALI circuit may not
exceed 128 mA (64 x 2 mA).
• Bus power and the DALI bus must be galvanically isolated from device
electronics for devices with bus power.
10.2 Bus topologies
64 operational devices
Up to 64 DALI operational devices may be installed on one DALI circuit. No
in a circuit
restrictions apply to the type mix.
Permissible bus topologies are: Tree, line, and star topologies. These topologies
can be mixed as needed. However, ring topologies are not allowed. Tree topology (with stub lines) Line topology (with loops)
N1 . N7 Operational devices
Mounting and installation
Building Technologies
10.3 Cables
The bus lines (= wired pair) are connected via DALI (DA).
Observe polarity.
Bus cable selection
Use standard off-the-shelf installation materials to wiring mains power. You must
observe the values indicated in this data sheet under "Technical data DALI". AC24V can be provided in the same (2 + 3 stands) or in a separate cable (5 wire).
Commonly used cable sizes (as per DIN VDE 0100/T520/Section 6): – NYM 5 x 1.5 mm2
A 1.5 mm2 cable corresponds to a AWG16 cable.
Distances
The overall length is 300 meters for a wiring cross-section of at least 1.5 mm2.
The permissible voltage drop off over the DALI line and the terminals is a maximum
of 2 V. The voltage drop off over the DALI line is typically 90% of 2V (1.8V) and via
the terminals 10% of 2V (0.2V).
. Regulations
Must comply with low-voltage installation regulations since the DALI signal is not
Faulty wiring
NO protection against miswiring with AC 24 V or AC 230 V:
Applying a voltage between DA+ / DA+ or between DA– / DA– wil destroy the
DALI PCB!
This is particularly the case when the AC 24 V supply plug is connected to
the DALI socket.
Mounting and installation
Building Technologies
10.4 Technical data DALI
Transmission medium (bus cable)
TP (twisted pair)
Bus line polarity
DA, DA (interchangeable)
Bus terminating resistor
Communication signal
The communication signal (information) is transferred symmetrically, i.e., as
voltage dif erence between the two bus lines (and not as a voltage dif erence to the
earthing potential). The sign preceding the voltage between DA+ and DA–
determines signal values 0 and 1.
2-wire, stranded (one wire pair)
5-wire, stranded
7-wire, stranded
Wiring cross section
Min. 1.5 mm2 (AWG16).
Distance (sum of all bus sections)
Note PXC3… devices do not have a connection for bus cable screens.
Bus power supply
Bus power through the PXC3… room automation DC 16 V, 128 mA.
(for max. 64 DALI devices)
Mounting and installation
Building Technologies
11 EnOcean RF networks
11.1 Technology
(This section is based on the document "EnOcean Range planning" by Engineer
Armin Anders, EnOcean LLC).
The patented EnOcean RF technology creates a surprisingly far-reaching signal
with remarkably little energy. So that devices can be operated trouble-free without
solar cells, Piezo elements or thermocouples. The patented EnOcean RF technology creates a surprisingly far-reaching signal
with remarkably little energy. So that devices can be operated trouble-free without
solar cells (for room temperature sensors) or Piezo elements (switches/buttons). At just 50 µWs, a standard EnOcean RF modules can transmit a signal over a
distance of 300 meters (in a free field). The secret is the signal duration is just one
one thousandth of a second and triggers, executes and concludes the entire
Figure: EnOcean technology uses
Summary of EnOcean RF standards
High reliability
• License-free frequency ranges 868 MHz or 315MHz at 1% duty cycle
(comply with local law/releases).
• Multiple telegram transmission with checksum.
• Short telegrams (ca. 1ms) results in a low probability of collisions.
• High range: 30 meters in buildings & 300 meters unhindered.
• Repeater available for extensions.
• Uni and bidirectional communications.
Low energy demand.
• High data transmission rate of 125 kbps.
• Low "data overhead".
• ASK modulation.
Mounting and installation
Building Technologies
EnOcean RF networks
• RF protocol is defined and integrated in the modules.
• Sensor profiles are established and followed by users.
• Unique transmission ID (32 bit).
Coexistence with other • No interference with DECT, WLAN, PMR systems, etc.
RF systems
• System design verified in an industrial environment.
Specially suited for
• Renovation projects (old buildings, museums, churches, historical buildings,
• Rooms where wall reworking is difficult or even impossible (sandstone, glass,
• Spaces requiring adjustable room division (open plan offices, museums, TV
• Rooms with flexible furnishing or frequently changing decor
• System extensions
Switches, sensors and actuators in building technology. Wireless range in building is ca. 30 m. For operation with a control unit, the connection to the gateway must first be set
up. See data sheet N1661 (Gateway EnOcean/LonWorks) or N1662 (Gateway
Typical application
(example with additional third-party components)
Temperature monitoring
Function
Data telegrams from EnOcean devices are received by the receiver (e.g. EnOcean
/ KNX Gateway) and forwarded as communications objects to the control unit. This type of cooperation requires that the receiver "trained" the sender. See data
sheet N1662 (Gateway EnOcean/KNX). Current room device data are sent only every ca. 15 minutes to consume as little
energy as possible. However, this signal, a so-called presence signal, is always
Mounting and installation
Building Technologies
EnOcean RF networks
sent. Moreover, some events are sent with a ca. 2-minute delay or immediately.
For details, see the technical data "Frequency of transmission". The room device stops transmitting if the energy store is not charged sufficiently
and/or the battery is empty. 100% functionality cannot be guaranteed under all circumstances. There are
simply too many possible sources of interference, both legal and il egal, impacting
range tremendously. This includes radio applications using the same frequency for
transmission, e.g. other control systems with wireless connection. In addition,
reflection based on room design or interior décor impacts signal quality and
transmission security.
Additional information
Detailed information is available on the EnOcean homepage at:
The EnOcean Al iance homepage includes a list of all manufacturers offering
compatible devices:
11.2 Lighting conditions at mounting location
This section refers to room units equipped with solar cel s. The data provided
below is based on QAX9x.4 room units. For guaranteed operation (without battery), at least 200 Lux il uminance must be
present for at least 3 to 4 hours daily. Avoid direct exposure to the sun, as this
results in fault temperature readings. Avoid also shading by furniture as well as
mounting in wall recesses without sufficient lighting. Startup time at empty energy store:
Approx. 1 min. at 400 lx
Il umination time required to charge the empty energy
Approx. 6 h at 400 lx 1), 2)
store for 14 hours operation in total darkness: Il umination time to recharge a working energy store for Approx. 2 h at 200 lx 1), 2)
14 hours operation in total darkness: Maximum operating time at 100% charge and total
darkness: 1) Sending a radio signal ca. every 15 minutes (average).
2) Typical value depending on prior charging of energy cell.
As brightness is hard to evaluate, we recommend control measurements using a
device to measure il uminance.
Mounting and installation
Building Technologies
EnOcean RF networks
11.2.1 Definition: Illuminance
Brightness refers to how the human eye perceives the intensity of a light source.
Brightness is measured in Lux [lx]. The human eye can perceive various light
sources with the same brightness. Depending on the technology, solar cells have
varying degrees of efficiency for daylight and artificial light. Fluorescent lights
require at least 30% greater brightness to generate the same level of charging as
daylight. The value of the product light (Lux) and duration (h) are referred to as Lux h. The amount of available daylight in the winter is minimal. Winter must be used for
calculations if the intent is to guarantee functionality. Of further note is that
il uminance dif ers on horizontal versus vertical surfaces. As a matter of principle,
horizontal surfaces are better then vertical, of course with the exception of roofs.
11.2.2 Minimum room conditions
The following minimum conditions must be guaranteed for the mounting location of
STM solar cel s: • Check the STM initialization parameters as described in the user's guide.
• Check light sources (daylight or artificial light). Assume a worst case involving
fluorescent lamps if the light source cannot be clearly defined.
• Define minimum brightness and duration of il uminance required to ensure
• Check lighting conditions on the planned mounting location for the module
assuming the least favorable conditions (e.g. in winter).
The energy cell drains too mush if the average il uminance drops below the
defined, indicated values and transmission ceases. Transmissions resumes
automatically as soon as the energy cell is sufficiently charged. The list provides typical il uminance values. Please use a Lux meter to measure
A satisfactory Luxmeter is available as of EUR 30.
Building type
Room type
Typical brightness
Class rooms in general
Reading rooms, labs
PC rooms, working on PCs
Manufacturing halls
Development, office
Labs and inspections
Product packaging
Mounting and installation
Building Technologies
EnOcean RF networks
First aide, surgery
11.2.3 Notes on mounting location of room units
• Select the best compromise between Il uminance, ventilation locations and
aesthetic requirements.
• Where possible, install room units opposite windows with the longest daylight
• Avoid recesses without sufficient daylight.
• With regard to future room use: Select a mounting location where the room unit
is not shaded by users (e.g. by moving around furniture).
Fig.: Examples for brightness on various locations in a typical office (desk EA = 500
Whether il uminance on the wall is actually 200 lx, depends in large measure on
local conditions. We recommend conducting reference measurements using a
luxmeter. A device with battery backup can be used is il uminance is insufficient
Mounting and installation
Building Technologies
EnOcean RF networks
11.2.4 Prior to commissioning
Solar energy cells must be charged prior to commissioning (especial y after storage
for long periods in darkness prior to initial installation). This occurs automatically as
soon as the solar cell is exposed to light. The device is fully operational after 3 to 4 days if the initial charge is not enough. The energy is now sufficient to ensure full functionality even after darkness (even
at night or on weekends for up to 90 hours).
11.3 Battery operation
This section refers to room units equipped with solar cells. Normally, ambient light suffices to charge the energy store required to operate the
room device. If, however, lighting conditions at the mounting location are
insufficient to meet guide values provided in Secti"Lighting conditions at
mounting location", insert a battery in the battery holder. This ensures device
operation even under unfavorable lighting conditions.
Use a lithium button cell battery (type CR2032).
It is widely available in electrical supply shops.
A battery can have a typical battery life of up to 5 years.
The battery wil be emptied sooner if the device is operated in total darkness and
radio telegrams are transmitted frequently. Battery-supported operation is neither necessary nor recommended if there is
suf icient light!
11.4 RF link properties
General information on
In Europe, room devices use frequency 868.3 MHz and 315 Mhz reserved for this
"radio signals"
purpose. This frequency may be used for various applications (ISM) with some
limitations. If radio signals on this frequency overlap and interfere, data transmission from a
room device to a receiver module may temporarily be impaired. The distance of
sender and receiver to various interference sources (e.g. audio/video systems,
computer) should at least be 50 cm.
Check sensitive medical devices using this frequency range in a case-by-case
Caution!
Used together with third-
For detailed information, see the description of the radio signal modules available
party receivers
for download at:
Mounting and installation
Building Technologies
EnOcean RF networks
11.4.1 RF signals
Radio signal range
A radio signal's strength decreases with distance as it is sent in all directions. In
addition, other factors influence the radio signal strength. Below are a few examples of interference and attenuating impact of dif erent
Material:
Passage of radio
uncoated glass Brick, pressboards 65.95 %
Avoid under all circumstances to
metal ical y
screen a room device.
Building materials as well as wall angles in particular influence the radio signal
range with the radio link. The greater the angle at which electromagnetic waves hit
a wall, the greater signal attenuation. As a result, avoid flat angles and wall niches.
Examples:
Radio signal Passage
RIGIPS wal s, dry
Brick walls, aerated Ca. 19 m
Reinforced concrete Ca. 10 m
Geringe Dämpfung
wal s Fire protection walls, The radio signal is isolated
elevator shafts,
stairwells, supply
Mounting and installation
Building Technologies
EnOcean RF networks
11.5 Planning RF networks
11.5.1 RF signal range
Send RF signals are electromagnetic waves, the field strength at the receiver
decreases as the distance to the transmitter increases, in other words, the RF rang
e is limited. Any materials in the transmission field reduces the range accordingly.
RF waves do penetrate walls, but dampen the strength versus pure line of sight.
Reduction in range from walls versus a free field of view:
Material
Reduction in range versus a
free field of view
Wood, gypsum, uncoated glass, without metal
Brick, pressboards
Reinforced cement
Metal, aluminum lamination
The
geometric shape of the room
determines the RF range, since
transmission is not in the form of rays,
but rather requires a certain room
volume (ellipsoid with sender Tx and
receiver Rx in both focal points).
At 30 meter in range, the ellipsoid
center diameter is theoretically
around 10 meters (868 MHz). Narrow Fig: Narrow hallways with large walls.
hallways with large walls are
The
antenna setup and the
distance from ceilings, floors and walls plays an
important role. Internal antennas typically have better RF properties versus flush-
mount receivers. People and objects in the room also reduce range. The generally
standard range of "30 meters in buildings" should be viewed in a dif erential
manner dues to the numerous influences. Planning for reserves in the range is
necessary to achieve a reliable function of the RF system, even under unfavorable
Robust and reliable instal ation in buildings is achieved by ensuring
sufficient range reserves.
Practical hints
•
> 30 meter for very good conditions: Large free space, optimum antenna
installation and placement.
•
Planning security with furniture and people in the room, through up to 5
gypsum drywall or 2 brick/aerated concrete:
–
> 20 meters for transmitters and receivers with solid antenna execution and
–
> 10 meters for received installed in the room wall or corner. Or small
receives with internal antennas. Also together with switches on or wire
antenna near metal. Or narrow hallway.
• Vertical through 1-2 room corners depending on fixtures and antenna execution.
• Learning by EnOcean devices can greatly increase availability. A receiver can
work with multiple, received signals.
Mounting and installation
Building Technologies
EnOcean RF networks
11.5.2 RF signal shielding
Metal surfaces reflect electromagnetic waves, e.g. metal partitions and metal
ceilings, massive steel reinforcement in the concrete walls and metal foils from
insulation. Creating RF shading in a "silent zone". Individual, thin metal strips have
little impact, for example, strips in a gypsum drywall.
Metal surfaces
Mounting a transmitter directly on a metal surface (e.g. panel doors, steel door
frames) prevent the free transmission of the RF signal. This may impact RF
connection or even cause a loss of connection. Functions are only possible as an
exception for a device mounted in this manner and cannot be guaranteed
Metal partitions
RF technology does work with metal room partitions. The signals are reflects: Metal
and concrete walls reflect RF waves. RF waves penetrate to neighboring hallways
or rooms through opening, e.g. a wood door or glass partition. The range can be
significantly reduced based on the specific local conditions. An additional repeater
in the right place is an easy way to provide and alternative RF path.
An EnOcean RF signal can be amplified at most two times by a repeater.
Factors reducing range
• Metal partitions or hallow walls with insulation on metal foil.
• Suspending ceilings with panels made of metal or carbon fibers.
• Steel furniture or glass with metal coating.
• Mounting the switch on a metal wall (typically results in a loss of 30% in range).
• User of metal switch frames (typically results in a loss of 30% in range).
Fire protection walls, elevator shafts, stairwells and supply areas should be
considered shielding.
Solution
You can eliminate shielding by repositioning the transmitter and/or receiver
antenna from the silent zone or using a repeater.
Mounting and installation
Building Technologies
EnOcean RF networks
11.5.3 Penetration angle
The angle at which a transmitted signal hits the wall plays an important role. The
effective wall strength and thus the dampening of the signal depends on the angle.
The signals should run vertical to the walls as much as possible. Avoid wall
recesses as much as possible.
Solution
Eliminate excessively flat penetration angles by repositioning the transmitter and/or
receiver antenna or use a repeater.
11.5.4 Mounting the antenna
Do not mount the receiver antenna or a receiver with internal antenna on the same
wall as the transmitter. RF waves are subject to disruptive refraction or reflection
near walls. It is better to mount the receiver on the next or opposite wall. The
antenna for devices with featuring external antennas should be mounted in a
centralized location in the room. Where possible, the antenna should be at least 10
cm from corners or cement ceilings.
Avoid RF transmission along wall surfaces (e.g. in a long hallway as
The ideal mounting location of the receiver's antenna is a central location in the
room. "Magnetic foot antenna" (e.g. Hirschmann MCA 1890 MH) must attach to a
large a metal surface as possible to provide a sufficient counter polarity. For
example, mounting the antenna on a ventilation duct. Conversely, a "patch
antenna" (surface antenna, e.g. HAMA MiniPlanar 38499) must be mounted in a
non-metal ceiling or drywall, for example, in a cavity wall socket of the right size
(see image below). A patch antenna cannot normally be mounted directly in cement
or in direct proximity to metal. One exception is the "metal patch antenna MCA
1890MP" by the Hirschmann company. The flat antenna can be attached discretely
Mounting and installation
Building Technologies
EnOcean RF networks
and directly to a metal ceiling. For additional details on selected suitable plugs,
please refer to the application note "AN103 External Antennas" by EnOcean.
Mounting magnetic foot antenna Mounting patch antenna
Then laying the antenna cable it is important not to bend the cable,
causing irreparable damage (reduction in performance caused by a
change to wave resistance).
A "active antenna" is a RF receiver with integrated antenna. It communicates with
an actuator unit, for example, via a simply RS485 cable (RS485 Gateway). So that
no shielded antenna is required that suffers from reduced performance as the
length increases and that can be bent during installation.
11.5.5 Distances from receive to other sources of interference
EnOcean
transmitters can be placed next to any transmitter without a problem.
Conversely, the distance from the EnOcean
receiver to other transmitters (e.g.
GSM / DECT / Wireless LAN) and high frequency sources of interference
(computer, audio and video systems) must be at least 50 cm.
The distance of the EnOcean receiver to other high frequency transmitters
should be at least 50 cm.
The transmitter position is non-critical.
Mounting and installation
Building Technologies
EnOcean RF networks
11.5.6 Repeaters
Repeaters (i.e. amplifiers) can help overcome problems with reception quality. The
EnOcean repeater requires no configuring (e.g. self learning). Simply connect to
the supply voltage to commission. The Sections on "Shielding" and "Penetration"
include il ustration on possible deployment.
Post-installation of repeaters should be considered (electrical connection)
during planning for unfavorable situations. Too many repeaters is
counter-productive (higher costs, collision of telegrams).
EnOcean repeaters cannot be cascaded in their "1-level" basic function, previously
repeated telegrams wil not be repeated again. Repeaters switchable to 2-level
function do allow for cascading via two repeaters. But it should only be used under
exceptional building-technical cases.
11.5.7 Field strength measuring equipment
Of -the-shelf field strength measures devices that easily find the best mounting
locations for transmitter and receiver. Faulty connection from previously installed
devices can also be reviewed. The RF telegrams and disruptive RF signals are
displayed in the relevant frequency range. Additional information available at:
Mounting and installation
Building Technologies
EnOcean RF networks
11.6 Range planning
RF range is typically limited by fire protection walls that are considered shielding.
Within fire protection areas, light walls or glass partitions with solid RF properties
are often used. Avoid metal reinforcement or metalized glass!.
The following diagrams il ustrate how to implement a reliable RF plan in three
STEP 1: Floor plan and
STEO 2: Draw relevant
• Fire protection walls
RF shielding on the floor
Elevator shafts, stairwells and other supply areas
Mounting and installation
Building Technologies
EnOcean RF networks
STEP 3: Draw range
• The center of the circle represents the ideal position for RF gateways.
This allows for a shield-free connection in all corners of the fire protection section
(possible sensor positions).
Real-world experience suggests that unfavorable conditions and shortcomings are
commonplace. Planning at 10-12 meter radiuses provide a high level of security;
against future changes to environmental changes as well (light walls, furniture,
personnel in the room, etc.). One meter either way for the gateway position is not
an issue due to reserves, even later.
A very robust RF system can be achieved by implementing a redundant RF
reception path. This can be accomplished by programming neighboring RF
gateways for parallel reception of the RF transmitter.
Even if careful y planned, the field strength measuring device should be used on
site to test ranges. Unfavorable conditions can be improved through more suitable
re-positioning of the devices or through the use of a repeater.
Mounting and installation
Building Technologies
EnOcean RF networks
11.7 Troubleshooting
Trouble free operation of the devices is normally guaranteed if you follow all the
notes on the selection of mounting locations for transmitters and receivers. The
following overview of potential problems may help should problems nevertheless
Transmitter is not
Check with EPM100
Possible cause and solution
received
In close proximity to the transmitter Transmitter is not transmitting.
(ca. 20-50 cm distance), the EPM
Check transmitter: Solar-powered
100 does not receive any
transmitter is supplied with sufficient light
transmission telegrams.
as applicable (for quick function test,
Trigger transmission telegram, the
briefly expose the device to daylight or
LED HI is unlit on the EPM.
under a bright lamp).
In close proximity to the receiver
Transmitter mounted beyond the
(ca. 20-50 cm distance), the EPM
receiver range (or the transmitter was
100 does not receive any
removed in the meantime).
transmission telegrams.
Change the mounting location for the
Trigger transmitter telegram, the
transmitter or receiver, or use repeater.
corresponding LO/HI LED is unlit on
Comply with notes in Section 1.
EPM (HI for flush-mounted receiver,
LO for receiver with external antenna).
In close proximity to the receiver
a) Transmitter did not learn or
(ca. 20-50 cm distance), the EPM
incorrectly learned.
100 has solid reception of the
Have receiver self learn the transmitter.
transmitter telegram.
b) Receiver is not receiving.
Trigger transmission telegram, the
Check receiver, as needed, the receiver
LED HI is lit on the EPM.
antenna and cabling for antenna cable as
Invalid EnOcean telegrams are
a) High-frequency disruptions in the
permanently received.
vicinity of the receiver.
One of the two LO/HI LEDs is
Remove sources of interference (PC,
continuously lit on EPM 100, but not
wireless phone, etc., at least 50 cm from
EnOcean receiver).
b) Jammer (continuous transmission).
Eliminate jammer.
Mounting and installation
Building Technologies
EnOcean RF networks
Transmitter is
Check with EPM100
Possible cause and solution
occasionally not
In close proximity to the receiver
a) Transmitter is within the limits of
received
antenna (ca. 20-50 cm distance), the the transmitter.
EPM 100 receives transmitter
Move the transmitter or receiver antenna
telegram at the limits.
or use a repeater. Comply with notes in
Trigger transmission telegram, the
corresponding LO/HI LED is unlit on
b) Transmitter not installed where
(HI for flush-mount receiver; LO for
expected (or incorrectly assigned
receiver with external antenna).
Properly assign transmitter.
c) Transmitter mounting location
changes on occasion (e.g. not tightly
attached).
Move the mounting location of the
transmitter within the receiver range.
In close proximity to the receiver
Receiver is not receiving.
antenna (ca. 20-50 cm distance), the Check receiver, as needed, the receiver
EPM 100 has solid reception of the
antenna and cabling for antenna cable as
transmitter telegram.
Invalid EnOcean telegrams are
Jammer exists.
occasionally received.
Eliminate jammer.
One of the two LO/HI LEDs is
occasionally lit on EPM 100, but not
Mounting and installation
Building Technologies
EnOcean RF networks
11.8 Commissioning RF link
For operation, the connection to the gateway must first be set up. See data sheet
N1661 (Gateway EnOcean/LonWorks) or N1662 (Gateway EnOcean/KNX).
Send "Init" telegrams
The LEARN button is located on the lower
section of the housing below the battery.
Press this button to create and immediately send
a complete learning telegram. The current
switching status of LEARN – pressed – is also
transmitted. If the corresponding receiver is being configured,
the information helps assign a specific output
channel to the sender.
This procedure is referred to as "learning". A normal telegram does not initiate this
procedure.
Repeat the procedure if you want to assign
several output channels to one
Simple function check
The LEARN button allows for a simple function and range test.
Make sure the
room device was charged sufficiently prior to testing. Depending on receiver type and configuration, an LED indicates if the receiver
finds the LEARN button was pressed on a learned room device. No
acknowledgement occurs if the telegram is not received completely. Possible
causes: Distance too great or unfavorable mounting location with too many
interference sources within the radio link. Of -the-shelf field strength measures devices that easily find the best mounting
locations for transmitter and receiver. Additional information available at:
11.9 Gateways
Wireless room units together with a gateway (EnOcean/KNX) can be used with all
controllers on a PL-Link or KNX network.
EnOcean gateways
RXZ97.1/KNX S55842-Z101
Gateway EnOcean/KNX
Engineering KNX
See description of the gateway datasheet [12].
LONWORKS page
Mounting and installation
Building Technologies
EnOcean RF networks
12 Disposal
The devices are considered electronics devices for disposal in terms of
European Directive 2002/96/EC (WEEE) and may not be disposed of as
Dispose of the devices via the proper channels.
Follow all local and currently applicable laws and regulations.
Siemens Switzerland Ltd
Infrastructure & Cities Sector
Building Technologies Division
Tel. +41 41-724 24 24
2012 Siemens Switzerland Ltd
Subject to change
Mounting and installation
Building Technologies
Source: http://ibt.su/CM111043en.pdf
PASS CR (MICRO Type II) CAPE SEAL and PASS QB Rejuvenating Seal for Residential Roads SECTION 700 - PASS CR Scrub Seal The work shall consist of furnishing all necessary labor, materials and equipment for the transporting, application of the polymer modified asphaltic emulsion PASS or equal, ¼" by No. 10 premium aggregate to conform to the Provisions of Section 37-2, of the Standard Specifications, Plans and these Special Provisions. The work shall be done in the following order: preparing the pavement surface; applying the emulsion; scrubbing the applied emulsion with an emulsion broom; applying premium aggregate; rolling the ¼" by No. 10 premium aggregate; and sweeping up excess aggregate and more fully described below.
Education in the Round My Vision is Blurry: Could it be from any of the medications that I am taking? Mark T. Dunbar, OD, FAAO Director of Optometry Bascom Palme Eye Institute University of Miami, Miller School of Medicine Miami, FL 33136 Mark Dunbar: Disclosure • Consultant for Allergan • Optometry Advisory Board for: